Accessory List
453L, 453H, 453R Series
2
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Model Chart (Continued)
Specifications
Model No. Description
Voltage
Vac
Drive
Direction
of
Rotation
a
a
Drive direction as viewed from the bottom of the actuator.
Torque Rating in.-oz. Stroke Speed in Seconds
Motor Driven
Spring
Return
Motor
Driven
Spring
Return
0° 84° 0° 84°
453H0077GA01 Direct Drive with End Switch 24
CCW 55 35 35 55
27 @ 60 Hz
32@ 50 Hz
8 @ 50/60 Hz
453H0077GB00 Direct Drive
120
453H0077GB01 Direct Drive with End Switch
453H0077GU00 Direct Drive 230
453L0038GA00
24
CW
45 25 17 25
18 @ 60 Hz
22@ 50 Hz
6 @ 50/60 Hz
453L0038GA01
Linkage Drive with End
Switch
453L0038GB00 Linkage Drive
120
453L0038GB01
Linkage Drive with End
Switch
453L0038GU00 Linkage Drive
230
453L0038GU01
Linkage Drive with End
Switch
453L0074GA00
Direct Drive
24
CCW453L0074GB00 120
453L0074GU00 230
453L0077GA00
24
CW
453L0077GA01 Direct Drive with End Switch
453L0077GB00 Direct Drive
120
453L0077GB01 Direct Drive with End Switch
453L0077GU00 Direct Drive
230
453L0077GU01 Direct Drive with End Switch
453R0077GA00
Direct Drive 3-wire Control
24
—150150——
37 @ 60 Hz
45 @ 50 Hz
Non-Spring
Return
453R0077GB00 120
453R0077GU00 240
Inputs
Control signal SPST for spring return, SPDT for non-spring return.
Power
24 Vac @ 50/60 Hz; 110/120 Vac @ 50/60 Hz; 220/230 Vac @ 50/60 Hz.
453L, 453R: 6.5 W, 7 VA. 453H: 6.5W, 10 VA.
End switch: 10 Amps @ 120 Vac.
Outputs
Motor Type Synchronous AC.
Mechanical
Direction of rotation: CW or CCW rotation.
Maximum close-off torque: See Model Chart.
Environment
Ambient temperature limits
Shipping and storage: -40 to 169°F (-40 to 71°C).
Operating: 0 to 120°F (-17 to 49°C).
Humidity Non-condensing.
Locations NEMA Type 1.
Agency Listings
UL File #E37601.
CSA File #LR19535 listed, CE compliant.
General Instructions Refer to F-27028.