Accessory List
MF51-7x03 Series, MF61-7203
126
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Typical Applications
MFx1-7x03-xxx
MF61-7203
24 Vac Transformer
or 20-30 Vdc
Red
Black
Common
1
Hot (+DC)
Line
Volts
Blue
Retract
Extend
Yellow/Black
Typical
Floating
Controller
(-)
(+)
Feedback Signal
2 to 10 Vdc
Violet
2 3
1 Provide overload protection and disconnect as
required. If controller uses a full wave power
supply and does not provide isolated outputs, a
separate transformer must be used.
2 Actu
ators may be wired in parallel. All actuator
black wires are connected to the transformer
common and all red wires are connected to the hot
lead. Power consumption must be observed.
3 Cable on some models
contains more wires than
are used in applications. Only those wires actually
used are shown.
4 Feedback only available on MF51-7103 models.
4
Figure 1 Floating Point Control.
MFx1-7x03-xxx
MF61-7203
24 Vac Transformer
or 20-30 Vdc
Red
Black
Common
Hot (+DC)
1
Line
Volts
Controller
Blue
Yellow/Black
Hot
Common
Retract
Extend
(-)
(+)
Feedback Signal
2 to 10 Vdc
Violet
2 3
4
1 Provide overload protection and disconnect as
required. If controller uses a full wave power
supply and does not provide isolated outputs, a
separate transformer must be used.
2 Act
uators may be wired in parallel. All actuator
black wires are connected to the transformer
common and all red wires are connected to the hot
lead. Power consumption must be observed.
3 Cable on some model
s contains more wires than
are used in applications. Only those wires actually
used are shown.
4 Feedback only available on MF51-7103 models.
Figure 2 Triac Source.
MFx1-7203
MFx1-7x03-xxx
Red
Black
Common
Hot (+DC)
1
Line
Volts
Controller
Blue
Yellow/Black
Hot
Common
2
Retract
Extend
24 Vac
Transformer
or 20-30 Vdc
(-)
(+)
Feedback Signal
2 to 10 Vdc
Violet
AO
3
2 The Common connection from the actuator must be
connected to the Hot connection of the controller. The
actuator Hot must be connected to the controller
Common.
3 Cable on some models contains more wires
than are used in applications. Only those
wires actually used are shown.
1 Provide overload protection and disconnect as
required. If controller uses a full wave power supply
and does not provide isolated outputs, a separate
transformer must be used.
4
4 Feedback only available on MF51-7103 models.
Figure 3 Triac Sink.
1
Line
Volts
24 Vac Transformer
or 20-30 Vdc
MFx1-7203
MFx1-7x03-xxx
Red
Black
Common
Hot (+DC)
1
Line
Volts
Controller
Blue
Yellow/Black
Hot
Common
Retract
Extend
24 Vac Transformer
or 20-30 Vdc
(-)
(+)
Feedback Signal
2 to 10 Vdc
Violet
AO
2
3
2 Actuators may be wired
in parallel. All actuator black wires are connected to
the transformer common and all red wires are
connected to the hot lead. Power consumption must
be observed.
3 Cable on some models contains more wires
than are used in applications. Only those
wires actually used are shown.
1 Provide overload protection and disconnect as
required. If controller uses a full wave power supply
and does not provide isolated outputs, a separate
transformer must be used.
4
4 Feedback only available on MF51-7103 models.
Figure 4 Triac Sink With Separate Transformers.