MF40-7173
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 105
Accessories
Specifications (Continued)
Outp
uts
Motor Type Brushless DC.
Mechanical
Direction of rotation: CW or CCW rotation is available through reverse mounting.
Dual shaft clamp: Direct coupled using a through hole output hub.
Stroke: Electronically limited to 93° ± 1°.
Environment
Ambient Temperature limits
Shipping and storage: -40 to 160°F (-40 to 71°C).
Operating: -25 to 140°F (-32 to 60°C).
Humidity 5 to 95% RH, non-condensing.
Locations NEMA 1, NEMA 4 (IEC IP56) with customer supplied water tight connector.
Dimensions 10-27/32 H x 4 W x 4 D in. (280 x 100 x 100 mm).
Agency Listings
UL
UL-873, Underwriters Laboratories Listed (File #9429 Category: Temperature-Indicating and
Regulating Equipment.)
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
CUL Canadian Standards C22.2 No. 4-93.
Australia
This product meets requirements to bear the C-Tick mark according to the terms specified by the
Communications Authority under the Radio Communications Act 1992.
General Instructions Refer to F-26749.
Model No. Description
AM-674 Weather shield.
AM-676 Universal shaft extension, approximately 9-1/2 in. long (242 mm) for use on 3/8 to 11/16 in. (10 to 17 mm)
round shafts, 3/8 to 9/16 in. square shafts. (AM-753 clamps required).
AM-751 Standard anti-rotation bracket 9 in. long x 13/16 in. wide (229 x 21 mm), included with actuator.
AM-752 Optional anti-rotation bracket 4 in. long x 1-11/16 in. wide (102 x 43 mm), for narrow spaces.
AM-753 Damper shaft mounting clamps for 5/8 in. square shaft, 3/4 in. and 1 in. round shafts (two per package).
AM-754 Standard universal mounting clamps for 3/8 to 1/2 in. (10 to 13 mm) round and square shafts, two included
with actuator.
AM-756 Metric conduit adaptor M20 x 1.5 to 1/2 in. NPT (two per package).
AV-602 Valve linkage for VB-7xxx 1-1/2 to 2 in.
AV-607 Valve linkage for VB-9xxx 2-1/2 to 4 in.