Datasheet
Harmonic 
Measurement 
range 
Resolution 
Accuracy 
Harmonic number 
1 ~ 50 
Interharmonic 
1 ~ 49 
Harmonic voltage 
0.0 ~ 100.0% 
0.1% 
±0.1%±n×0.1% 
Harmonic current 
0.0 ~ 100.0% 
0.1% 
±0.1%±n×0.1% 
THD 
0.0 ~ 100.0% 
0.1% 
±2.5% 
DC relative 
0.0 ~ 100.0% 
0.1% 
±0.2% 
Frequency 
0 ~ 3500 Hz 
1 Hz 
1 Hz 
Phase 
-360° ~ 0° 
1° 
±n×1.5° 
Power & Energy 
Measurement 
range 
Resolution 
Accuracy 
Active power, apparent 
power, reactive power 
1.0 ~ 20.00 MW 
0.1 kW 
±1.5±10 characters 
Kilowatt-hour 
0.00 kWh ~ 200GWh 
10 Wh 
±1.5±10 characters 
Power factor 
0 ~ 1 
0.01 
±0.03 
Displacement power factor 
0 ~ 1 
0.01 
±0.03 
Unbalance 
Measurement 
range 
Resolution 
Accuracy 
Voltage unbalance 
0.0 ~ 5.0% 
0.1% 
±0.5% 
Current unbalance 
0.0 ~ 20.0% 
0.1% 
±1% 
Voltage phase 
-360° ~ 0° 
1° 
±2 characters 
Current phase 
-360° ~ 0° 
1° 
±5 characters 
Rapid range of voltage 
Measurement 
range 
Resolution 
Accuracy 
Voltage 
-  Vpk 
-  Vrms 
±6000 Vpk 
10 ~ 1000 Vrms 
1 V 
1 V 
±15% 
±2.5% 
Minimum test time 
50 μs 
Sampling rate 
20 kS/s 
Inrush current 
Measurement 
range 
Resolution 
Accuracy 
Arms 
0 ~ 3000 Arms 
0.1 
±1%±5 characters 
Inrush evaluation time 
6s ~ 32 min settable 
10 ms 
±20 ms 
8.8 Wiring Combinations 
1Ø+NEUTRAL 
Single phase with neutral 
1Ø SPLIT PHASE 
Split phase 
1Ø IT NO NEUTRAL 
Single phase system with two phase voltages without neutral 
3Ø WYE 
3-phase 4-wire system, Y type 
3Ø DELTA 
3-phase 3-wire system delta (Delta) 
3Ø IT 
3-phase Y type without neutral 
3Ø HIGH LEG 
4-wire 3-phase delta system (Delta) with center tapped high leg 
3Ø OPEN LEG 
Open-delta (Delta) 3-wire system with two transformer windings 
2-ELEMENT 
3-phase 3-wire system without current sensor on phase L2/B (2 Watt 
meter method) 
2
2
1
-ELEMENT 
3-phase 4-wire system without voltage sensor on phase L2/B 
-73- 