Datasheet
The table below gives a survey of the aspects of Power Quality Monitoring:  
Parameter 
Available Bar 
Graphs 
Limits 
Averaging Interval 
V rms 
3, 
one for each phase 
Probability 100%: upper & lower 
limits 
Probability x %: upper & lower 
limits 
10 minutes 
Harmonics 
3, 
one for each phase 
Probability 100%: upper limit 
Probability x %: upper limit 
10 minutes 
Flicker 
3, 
one for each phase 
Probability 100%: upper limit 
Probability x %: upper limit 
2 hours 
Dips/ 
Interruptions/ 
Rapid Voltage 
Changes/ 
Swells 
4, 
one for each 
parameter covering all 
3 phases 
Allowed number of events 
1/2 cycle rms based 
Unbalance 
1, 
covering all 3 phases 
Probability 100%: upper limit 
Probability x %: upper limit 
10 minutes 
Frequency 
1, 
measured on 
Reference Voltage 
Input A/L1 
Probability 100%: upper & lower 
limits 
Probability x %: upper & lower 
limits 
10 seconds 
 Power Quality main screen 
Power  Quality  Monitoring  is  reached  via  the  【MONITOR】key,  and  Immediate  or  Timed  start  is 
settable. With the direction keys you can position the Cursor on a particular Bar Graph. Measuring data 
belonging to the bar is shown in the screen header. 
Detailed measurement data is available under the Function keys: 
F1 
RMS voltage: events table, trends. 
F2 
Harmonics: bar graphs, events table, trends. 
F3 
Flicker: events table, trends. 
F4 
Dips/Interruption/Rapid Voltage Change/Swells: events table, trends. 
F5  
Unbalance, frequency: events table, trends. 
The measuring data available under the Function keys is explained in the following sections. Data is 
presented in the formats Events Table, Trend Display and Bar Graph Screen. 
-68- 