Datasheet
7.10. Inrush currents 
Inrush currents can be captured by the Analyzer. Inrush currents are surge currents that occur when a 
large, or low-impedance load comes on line. Normally the current will stabilize after some time when the 
load has reached normal working condition. For example the start-up current in induction motors can be 
ten times the normal  working  current.  Inrush  is  a  ‘single  shot’  mode  that  records  current  and  voltage 
Trends  after  a  current  event  has  occurred.  An  Inrush  occurs  when  the  current  waveform  exceeds 
adjustable limits. The Trends builds up from the right of the screen. Pretrigger information allows you to 
see what occurred in advance of the inrush. 
 Trend display 
Use the arrow keys in the Start menu to adjust the trigger limits: expected inrush time, nominal current, 
threshold  and  hysteresis. The  maximum  current  determines  the  vertical  height  of  the  current  display 
windows.  Threshold  is  the  current  level  that  triggers  the  trend  capture.  The  inrush  time  is  the  time 
between trigger and the time that the current falls to the value indicated by Hysteresis and is indicated on 
the trend display between two vertical markers. The screen header displays the rms of all phases during 
the inrush time. If the Cursor is on, the rms measuring values at the Cursor are displayed. 
Available function keys: 
F1 
Switch parameters to be displayed. 
F3 
Access to Cursor. 
F4 
Selection of Zoom or Cursor. 
F5 
Switch between RUN and HOLD. 
 Tips and Hints 
Check the inrush currents and their duration, use the Cursor for readout of momentary values. Check if 
fuses, circuit breakers, and conductors in the power distribution system can withstand the inrush current 
during this period. Check also if phase voltage stay stable enough. 
High peak currents can cause circuit breakers to trip unexpectedly. Measuring Inrush current can help in 
setting trip levels. Since the Analyzer simultaneously captures Inrush current and voltage Trends, you 
can use this measurement to check voltage stability as large loads come on line. 
-66- 










