Datasheet
 Bar Graph Screen 
The  Bar  Graph  display  shows  the  percentage  contribution  of  each  of  the  components  related to  the 
fundamental or full signal. A signal  without distortion should show a 1st  harmonic at  100% while the 
others are at 0: in practice this will not occur because there always is a certain amount of harmonics 
resulting in distortion. 
A sinewave becomes distorted when harmonics components are added to it. Distortion is represented by 
the Total Harmonic Distortion (THD) percentage. The display can also show the percentage of the DC 
component and each harmonic ratio. 
The left/right arrow keys are used to position the Cursor on particular bar. The screen header will show 
for that bar phase identifier, harmonic component ratio, frequency and phase angle. If not all bars are 
shown on the screen, you can bring the next set within the viewing area by moving the Cursor off the left 
or right end of the screen. 
Available function keys: 
F1 
Selection of harmonics type: 
voltage, current. 
F2 
Selection of bar set to be displayed: 
L1, L2, L3, N or all 
F3 
Interharmonics display on/off 
F4 
Open the table screen 
F5 
Switch between RUN and HOLD. 
 Table Screen 
The  table  screen  lists  all  the  harmonic  parameters,  including  Harmonic  Voltage,  Harmonic  Current, 
Interharmonic Voltage and Simple Harmonic Current. Select next page with up/down keys. 
Available function keys: 
F3 
Take fundamental voltage as percentage reference (%f) or total harmonic voltage as 
percentage reference (%r) 
F4 
Open the bar graph screen of harmonic 
F5 
Switch between RUN and HOLD. 
 Tips and Hints 
The harmonic number indicates the harmonic frequency: the first harmonic is the fundamental frequency 
(60 or 50Hz); the second harmonic is the component with two times the fundamental frequency (120 or 
100Hz), and so on. The harmonics sequence can be positive (1, 4, 7…), zero (3, 6, 9…) or negative (2, 
5, 8…). Positive sequence harmonics try to make a motor run faster than the fundamental, negative 
sequence harmonics try to make a motor run slower than the fundamental. In both cases the motor 
looses torque and heats up. Harmonics can also cause transformers to overheat. Even harmonics 
disappear if waveforms are symmetrical, i.e. as equally positive and negative. 
Zero sequence current harmonics add in Neutral conductors. This can cause overheating of these 
conductors, and make ground potential rising.. 
-61- 










