Datasheet
7. Application examples 
7.1 Scope 
Scope mode shows voltages and currents in the power system under test by means of waveforms. Also 
numerical  values are  shown  such  as  phase  voltages,  phase  currents  and frequency  etc.  The  Scope 
waveform screen offers an oscilloscope style of display of  voltage and current waveforms with a fast 
update rate. The screen header shows the  related  rms  voltage/current values. Channel A (L1) is the 
reference channel, starting at 0V are displayed. 
Available function keys: 
F1 
Selection of 
waveform set 
to be displayed 
V displays all voltages; A displays all currents. A (L1), B (L2), C (L3), N 
(neutral) give simultaneous display of phase voltage and current for the 
selected phase. 
F3 
Access to 
cursor 
When the Cursor is on, the waveform values at the Cursor are displayed 
in the screen header. 
F4 
Selection of 
Zoom function 
and Cursor 
move function. 
When the Cursor is selected, press left/right arrow keys to move the 
cursor; when the Zoom function is selected, press direction keys to 
expand or shrink waveforms. 
F5 
Switch between HOLD and RUN 
7.2 Voltage/Current/Frequency 
This  function  is  used  for  measuring  steady  voltage,  current,  frequency  and  crest  factors.  The  Crest 
Factor (CF) indicates the amount of distortion: a CF of 1.41 means no distortion and higher than 1.8 
means high distortion. Use this screen to get a first impression of power system performance before 
examining the system in detail with other measuring modes. 
7.3. Table screen 
The number of columns in the Table screen depends on the power system configuration. The figures in 
the Table screen are present values that may update constantly. Changes in these values over time are 
recorded as soon as the measurement is turned on. The recording is visible in the Trend screen. 
Available function keys: 
F1 
Under 3-phase Y type wiring configuration, switch between voltage readings of each 
phase (A/L1, B/L2, C/L3,N)or phase-phase (AB, BC, CA). 
F4 
Access to the Trend screen. 
F5 
Switch between HOLD and RUN. 
-56- 