Datasheet
 Monitor limits 
The  Analyzer presets  a  set  of  limits  according  to  EN50160  standard,  and  reserves two  user-defined 
options, which the users can modify under EN50160 standard set of limits and save as user-defined set 
of limits. 
Use the up/down arrow keys to move  the highlighted row, then press【ENTER】 key radio button to 
select highlighted row. Selected by the radio button means this set of limits is currently active.  
Press 【F4】to access to limits edition interface and edit current highlighted set of limits, a survey of 
monitor limits adjustments: 
Limits 
Adjustments 
Voltage 
2 probability percentages (100% and adjustable): each with 
adjustable upper and lower limits. 
Harmonics 
For 2-25 harmonics and THD 2 probability percentages (100% and 
adjustable): each with adjustable upper limit. 
Flicker (*) 
Weighing curve (lamp type). 2 probability percentages (100% and 
adjustable): adjustable percentage with adjustable upper limit. 
Dips (*) 
Threshold, hysteresis, allowed number of week. 
Swells (*) 
Threshold, hysteresis, allowed number of week. 
Interruption (*) 
Threshold, hysteresis, allowed number of week. 
Rapid Voltage Change (*) 
Voltage tolerance, steady time, minimum step, minimum rate, 
allowed number of week. 
Unbalance 
2 probability percentages (100% and adjustable): adjustable 
percentage with adjustable upper limit. 
Frequency 
2 probability percentages (100% and adjustable): each with 
adjustable upper and lower limits. 
(*): Setups are also valid for measuring mode. 
6.7. Using Memory and PC 
The Analyzer can save screens and data into its memory, and the users can view, delete and copy them. 
The Analyzer can also be connected with a PC, through which the remote  control of the Analyzer is 
available. 
 Using memory 
The Analyzer has a built-in 8G TF card to store data the users saved. The Analyzer can save screenshot 
of current screen, and data set of current measurement too.  
 SAVE interface 
The 【SAVE】 key accesses save interface, select screenshot or data set as save type, the name of the 
file to be saved is editable. 
Press 【F1】 to switch save type. Use left/right arrow keys to move the cursor, and up/down keys to 
change  name, press【F4】SPACE  to  erase  current  selected character, the  cursor  moves  to  its next 
position. Press 【F5】to save the setting and return to previous interface. 
-54- 