Specification

R-25209_000 2021 07 06 RPT - Peak AQ PLUS - 2021 ISPSC.docm Page 3
N/A 305.2.5 Where the barrier is composed of
horizontal and vertical members and
the distance between the tops of the
horizontal members is less than 45
inches, the horizonal members shall be
located on the pool or spa side of the
fence. Spacing between vertical
members shall not exceed 1-¾ inches in
width.
Aquatine PLUS top and
bottom rails spaced 45-½
inches apart.
Conform 305.2.6
Where the barrier is composed of
horizontal and vertical members and
the distance between the tops of the
horizontal members is 45 inches or
more, spacing between the vertical
members shall not exceed 4 inches.
Aquatine PLUS barrier
vertical members have 4
inch maximum spacing
in between members.
N/A 305.2.7 The maximum opening formed by a
chain link fence shall be not more than
1-¾ inches.
Aquatine PLUS system
has no chain link
barriers.
N/A 305.2.8 Where the barrier is composed of
diagonal members, the maximum
opening formed by the diagonal
members shall be not greater than 1-¾
inches. The angle of diagonal members
shall be not greater than 45 degrees
from the vertical.
Aquatine PLUS barrier
has no diagonal
members.
Conform 305.2.9 Where equipment, including pool
equipment such as pumps, filters and
heaters, is on the same lot as a pool or
spa and such equipment is located
outside the barrier protecting the pool
or spa, such equipment shall be located
not less than 36 inches from the outside
of the barrier.
Aquatine PLUS barrier
requires 48 inch clear
zone on both sides of
the fence.
Conform 305.3
Door and gates in barriers shall comply
with the requirements of Sections
305.3.1 through 305.3.3 and shall be
equipped to accommodate a locking
device. Pedestrian access doors and
gates shall open outward away from the
pool or spa, shall be self-closing and
shall have a self-latching device.
Aquatine PLUS gate is
equipped with self-
latching device, hinge
self closes, opens away
from the pool.
N/A 305.3.1 Doors and gates not intended for
pedestrian use, such as utility or service
doors and gates, shall remain locked
when not in use.
This does not apply. No
utility or service doors or
gates in the system.
N/A 305.3.2 Double doors and gates or multiple
doors and gates shall have not fewer
than one leaf secured in place and the
adjacent leaf shall be secured with a
self-latching device.
No double or multiple
doors or gates in the
system.