Datasheet

Dokumentennummer: TK-DB-009 V5
Industriesteckgeräte
PC Electric GesmbH
Diesseits 145
A-4973 St. Martin/I., Austria
Internet: http://www.pcelectric.at
Tel.: +43 (0) 77 51 / 61 22 0
Fax: +43 (0) 77 51 / 69 69
Datasheet
1. Article: Enclosures for switchgear and controlgear assemblies
Description
Dimensions
WxHxD (mm)
Protection
Degree
Window up to
(modules)
9036*** / Anif
9134*** / Anif4
9135*** / Anif7
222x320x140
222x320x114
222x320x140
IP54 (IP66/IP67) 0, 10, 2x10
1.1. 4 fixing-holes inside and/or outside
1.2. protection class II (standard)
1.3. brass-nuts for the cover-fixing
1.4. non-losable screws for the cover
1.5. hinges between bottom and cover
2. Material features:
2.1. General
2.1.1. excellent impact resistance
2.1.2. high temperature and deformation resistance
2.1.3. very good electrical insulating qualities
2.1.4. weathering-, UV-resistant according to ISO 4892-2
2.1.5. good ozone resistance
2.1.6. site of installation: outdoor and indoor
2.1.7. good aging- and corrosion resistance
2.1.8. resistant to a diversity of oils, light acids, bases
2.2. Enclosure in PC/ABS
2.3. Empty enclosure conform to EN 62208
2.3.1. Glow-wire-resistance 750°C according to EN 60695-2-11
2.3.2. HB to UL94
2.3.3. Rated insulation voltage: 690V AC and 1500V DC
2.3.4. high mechanical strength, IK08 according to EN 50102 / EN 62262
2.3.5. heat dissipation.: 35W (30W) with surface mounted wall mounting as
single enclosure
2.3.6. bearing strength of DIN-rail: 10 Kg
2.3.7. ambient temperature: -25°C to +40°C
2.3.8. temperature of shipping and storage: -25°C to +55°C / short time 24h to
+70°C
2.3.9. special operating conditions must be agreed between PCE and the
operator
2.4. exposed screws for cover-fixing in V2A quality
3. Instruction:
It is the responsibility of each manufacturer to take care that all switchgear and
controlgear assemblies meet the safety requirement according to the conformity
standards. Technical modifications are reserved.