Data Sheet

GNM3D and GNM3T Series Communication Protocol
13
308196
2003h
1
RS485 Stop bit
UINT 16
Value 0 = 1 stop bit
Value 1= 1 (default)
Value 2 =2 (only if parity is even)
Any other value = 1 stop bit
308197
2004h
1
Max number of words readable
with a single Modbus request
UINT 16
Value = 50 (words)
Note: The number of stop bits is fixed to “1” if parity is EVEN.
2.
7.8 Reset commands
MODBUS: read and write mode Table 2.8-8
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
316385
4000h
1
Reset of all partial and tariff
meters, kWdmd and kWdmdm
peak
UINT 16
Value=0: reset done
Value=1: execute the command
All other values produce no effects
316386
4001h
1
Reset of total energy meters (only
for non-MID versions)
UINT 16
Value=0: reset done
Value=1: execute the command
All other values produce no effects
2.
7.9 Serial number
MODBUS: read only mode Table 2.8-9
Modicom
address
Physical
address
Length
(words)
VARIABLE
ENG. UNIT
Data
Format
Notes
320481
5000h
1
Letter 1 (from SX)
Letter 2 (from SX)
MSB: ASCII code
LSB: ASCII code
320482
5001h
1
Letter 3 (from SX)
Letter 4 (from SX)
MSB: ASCII code
LSB: ASCII code
320483
5002h
1
Letter 5 (from SX)
Letter 6 (from SX)
MSB: ASCII code
LSB: ASCII code
320484
5003h
1
Letter 7 (from SX)
Letter 8 (from SX)
MSB: ASCII code
LSB: ASCII code
320485
5004h
1
Letter 9 (from SX)
Letter 10 (from SX)
MSB: ASCII code
LSB: ASCII code
320486
5005h
1
Letter 11 (from SX)
Letter 12 (from SX)
MSB: ASCII code
LSB: ASCII code
320487
5006h
1
Letter 13 (from SX)
MSB: ASCII code
2.
7.10 Note
The default value shall be automatically assigned to the parameters when an out-of-range or invalid
value is written.