Data Sheet
Specification are subject to change without notice GNM3T
DS 221018
1
• Three phase energy meter
• Class B (kWh) according to EN50470-3
• Accuracy ±0.5% RDG (current/voltage)
• Current measurement via CT
• Backlit LCD display (3x 8-digit) with integrated touch
key-pad
• Energy readout on display: 8 digit
• Variable readout on display: 4 digit
•
Energy measurement: kWh and kvarh;
kWh+ by 2 tariffs; kWh per phase
• System variables: kW, kvar, kVA, VLL, VLN, PF, Hz,
kWdmd, kWdmd peak
• Phase variables: kW, kvar, kVA, VLL, VLN, A, PF
• Auxiliary power supply
• Dimensions: 3-DIN module
• Protection degree (front): IP51
•
Pulse output (GNM3T)
•
RS485 Modbus port (GNM3T-RS485)
•
M-bus port (GNM3T-MBUS)
• Run hour meter
• Neutral current calculation
Product description
Three-phase energy meter with backlit LCD display with integrated touch keypad. Particularly indicated for active
energy metering and for cost allocation (CT connection), with dual tariff management availability. It measures imported
energy (consumption). Housing for DIN-rail mounting, with IP51 front degree protection. The meter is optionally provided
with pulse output
proportional to the active energy being measured, RS485 Modbus port or M-bus port. Available for legal
metrology.
• Digital input (for tariff management
•
Certified according to MID Directive
Energy Management
Energy Meter
Type GNM3T, GNM3T-RS485, GNM3T-MBUS
How to order:
Certified according to MID Directive, Module "B" and Module "D" of Annex II, for legal metrology relevant to
active electrical energy meters (see Annex V, MI003, of MID). Can be used for fiscal (legal) metrology.
Range code
400 VLL AC - 5(6)A
(CT connection)
Power supply
H: auxiliary power sup-
ply 90 to 260V ac/dc
System
3:
3-phase, 3 or 4 wire
MID
GNM3T: Pulse output
GNM3T-RS485: RS485 port
GNM3T-MBUS: M-bus port