Installation guide

Table 11--Dry Coil Air Delivery* - Horizontal Downflow Discharge -
Unit PYIP018*060 (Deduct 10 percent for 208 Volts)
230 AND 460 VOLT
Unit Motor External Static Pressure (in. wg)
Speed 0.0 0.1 0.2 03 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 227 212 196 177 165 153 .....
Low
Cfm 1082 1016 929 796 668 428 .....
Watts ...........
618 Med
Cfm ...........
Watts 287 275 266 253 242 234 226 ....
High Cfm 1270 1179 1054 932 780 633 372 ....
Watts 280 275 270 267 264 262 260 ....
Low
Cfm 950 880 825 750 670 580 400 ....
Watts 380 375 365 360 355 350 344 335 312 -- --
624 Med
Cfm 1220 1150 1090 1025 970 860 760 620 450 -- --
Watts 485 475 470 460 455 445 437 430 415 385 --
High Cfm 1475 1440 1350 1275 1200 1125 1025 925 750 400 --
Watts 280 275 270 267 264 262 260 ....
Low
Cfm 950 880 825 750 670 580 400 ....
Watts 380 375 365 360 355 350 344 335 312 -- --
630 Med
Cfm 1220 1150 1090 1025 970 860 760 620 450 -- --
Watts 485 475 470 460 455 445 437 430 415 385 --
High Cfm 1475 1440 1350 1275 1200 1125 1025 925 750 400 --
Watts 576 566 556 536 512 497 481 466 450 435 --
Low
Cfm 1430 1403 1365 1263 1157 1068 973 900 827 704 --
Watts 680 671 660 624 604 620 602 558 534 512 496
636 Med
Cfm 1720 1630 1538 1439 1346 1267 1167 1126 1018 858 781
Watts 810 800 790 782 766 742 723 709 688 661 627
High Cfm 1800 1745 1660 1600 1547 1465 1360 1270 1163 967 876
Watts -- 675 660 650 640 630 620 610 595 580 --
Low
Cfm -- 1454 1387 1326 1275 1204 1142 1081 995 918 --
Watts -- 886 855 825 795 778 765 750 735 718 700
642 Med
Cfm -- 1515 1458 1406 1350 1285 1224 1163 1091 1013 932
Watts -- -- -- 1000 950 925 910 890 875 855 833
High Cfm -- -- -- 1551 1488 1424 1360 1296 1233 1148 1071
Watts -- 727 712 700 688 666 644 622 595 569 --
Low
Cfm -- 1678 1639 1600 1561 1500 1440 1379 1289 1198 --
Watts -- 853 836 821 807 782 756 730 699 667 640
648 Med
Cfm -- 1914 1870 1825 1780 1711 1642 1573 1470 1367 1270
Watts -- 979 959 943 927 897 868 838 802 766 730
High Cfm -- 2150 2100 2050 2000 1922 1845 1767 1600 1535 1419
Watts 1033 949 864 836 822 808 772 737 705 674 642
Low
Cfm 2105 2057 2009 1943 1909 1876 1823 1770 1698 1627 1531
Watts 1084 1054 1024 994 971 955 928 897 867 835 803
660 Med
Cfm 2318 2248 2179 2110 2058 2000 1932 1885 1829 1740 1638
Watts -- -- 1184 1152 1120 1102 1084 1056 1029 997 965
High Cfm -- -- 2349 2278 2207 2124 2041 2000 1960 1853 1745
* Air delivery values are without air filter and are for dry coil (See Table 14-PY1 P Wet Coil Pressure Drop).
NOTE: Deduct field-supplied air filter pressure drop and wet coil pressure drop to obtain external static pressure available for ducting.
UNIT SIZE
0'18,024, 030
036
042, 048, 060
Table 12--Filter Pressure Drop (In. wg)
FILTER SIZE
20X20X1
20X24X1
24X30X1
CFM
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
0.05 0.07 0.08 0.10 0.12 0.13 0.14 0.15
0.00 0.10 0.11 0.13 0.14 0.15 0.16
0.07 0.08 0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
1. Inspect air filter(s) each month. Clean or replace when necessary. Certain geographical locations may require more frequent inspections.
2. Inspect indoor coil, outdoor coil, drain pan, and condensate drain each cooling season for cleanliness. Clean at least once per heating /
cooling season or more often if needed.
3. Inspect blower motor and wheel for cleanliness at the beginning of each heating and cooling season. Clean when necessary. Forfirst heating
and cooling season, inspect blower wheel bi-monthly to determine proper cleaning frequency.
4. Check electrical connections for tightness and controls for proper operation each heating and cooling season. Service when necessary.
5. Ensure wires are not contacting refrigerant tubes or sharp sheet metal edges.
.....27....