Technical Specifications

Galvanized Steel Structural Deck Panels
The material presented in this publication has been prepared for the general information of the reader. The material is believed to be technically correct and in accordance with recognized good practice at the time of
publication. Advice should be sought with respect to its suitability for any specic application. Evolutiondeck Inc., its parent company, Casata Technologies Inc., its principals and employees expressly disclaim all liability for
errors or omissions in, and misuse or misinterpretation by others, or any damages (direct, indirect, incidental or consequential) whatsoever and howsoever caused, arising out of or in connection with the use of or in reliance
on the information included in this brochure. We reserve the right to change the information included herein without notication.
Galvanized Steel Structural Deck Panels
GUARD POSTS. Guard post (not exceeding 42-in. high)
to be installed max. 54 inches apart and through-bolted
through surface nish to steel deck using 4 @ 5/16” x L
diam. bolts per ASTM A307 or beer, with a 8”x10”x3/16”
steel sener bolted beneath per drawing. Sener may
be selected from min. SSMA 800S300-097 galvanized steel
channel (available from Evoluondeck Inc.), 8”x10”x3/16”
steel plate, (7a). Orient the channel sener perpendicular
to edge of deck supporng the guard post Field assembly
of railing or guard to be completed according to
manufacturer instrucons.
CUTTING. Panels may be cut in the eld. Addional
corrosion protecon is not be required on edges of
metallic-coated steel framing members, shop or eld cut,
punched or drilled.
INLINE FRAMING. Distributed or concentrated loads
from a roof column, raer, truss, and/or structural stud
requires a sener (fabricated from SSMA1000S300-097
steel channel, built-up laminated lumber or equiv.) in the
joist space beneath the point load aligned vercally over
a foong. Cumulave point loads from roof columns etc.
are to be aligned vercally with a suitable foundaon
support beneath.
LATERAL BRACING. Check with local ocials for specic
lateral condions. Ensure adequate stability of the
structure as a whole and adequate lateral, torsional and
local stability of all structural parts. Lateral bracing may be
achieved: (a) installing a 1/2” diam. x 6 in lag screw max.
24 inches on centre through bracket aached to the joist
web into rim joist or header of home; (b) installing a min.
24” steel channel (min. 1”x1” x 14ga or equiv.) from the
beam to a joist web using M12x1 self drilling fasteners, or
equiv.
SURFACE FINISHES. See paverdeck.com for surface nish
installaon. Compable surface nishes include:
stone or concrete pavers (0.75 to 3 in. thick). see
paverdeck.com
cast concrete (to 3 in.)
porcelain le, natural stone le rated for exterior use
composite or plasc decking (subject to
manufacturers warranty)
natural wood decking.
FASTENER CONNECTIONS. PAVERDECKtm systems are
assembled using all-weather M12 x 1 self-drilling screws as
described in ESR Report 1976 (Tek), ER-4780 (Dril-Flex),
ER-5454 (Pro-twist), ER-5280 (Grabber) or equivalent.
Fasteners into beams may be powder-actuated mechanical
fasteners with ballisc points and electroplated zinc
coang conforming to ASTM B 633, SC 1, Type III. Typical
Hil X-U-19 P8.
ASSEMBLY (SEE FIGURE 1).
1. At least one fastener will be located at all intersecons
between the structural beam, deck panels, and the starter
C-channel. Install the beam onto the foundaon columns
using standard brackets and fasteners.
2. Install the STARTER C-Channel over top of the BEAMS using
the supplied screw fasteners or powder actuated fasteners.
3. Then install rst INFIELD deck panel, seang the leading
right edge of the secon on top of the previously installed
STARTER. Secure this joint using the approved screws not
more than 3.0 inches from either end and 12.0 inches
between screws. Secure the boom ange onto the
structural beam using at least one fastener.
4. Connue adding and securing the INFIELD panels in a
similar manner along the width of the structure to the
desired width. Panels can be spaced from 10-11.0 inches
apart. A panel may be ripped along the diaphragm to a
custom width.
5. Install an End Panel secon as the last piece along the width
of the deck. This panel may be ripped lengthwisde through
for ng. Fascia cap is non-structural and can be installed
to over open joist space to support nish fascia material.
6. Surface nishes may be applied using known techniques
suitable to the nish employed. See www.paverdeck.com.
7. Locate guard post base ange min. 1” from edge of metal
deck, and install 4 bolts through clearance hole in surface
nish and through steel deckpan, using min. 5/16” diam. x
3.5” Gr. 2 galvanized steel bolts per ASTM A307 or beer.
Insert galvanized washers between bolts and base ange
and nuts and metal deck, with 8”x9” deck sener in
joist space beneath the post. Sener may be selected
from min. SSMA 800S250-097 galvanized steel channel
(available from Evoluondeck Inc.), 8”x9”x3/16” steel plate,
(7a). Orient the sener such that 2.5-inch anges are
perpendicular to edge of deck supporng the guard post
(see gure 1-B for various post conguraons).
8. Install oponal zinc anode system (R3 type zinc anode)
bolted through the joist web at a locaon accessible in the
future to inspect and replace the anode.
9. The beams and plaorm may be installed below grade, with
zinc anode system bolted through the joist web at a locaon
accessible in the future to inspect and replace the anode.
1
Beam
Foundation
Post
2
3
4
5
6
8
9
ANODE
7a
1
Foundation
Post
1 1/2"
1 1/2"
1 1/2"
(A) Guard post
flange on corner.
(C) Guard post
flange in centre
joist position.
(D) Guard post
flange in outside
corner position.
7a 7a 7a
7a
7
7
7
2
3
5
7
7
7
7
Rail post flange
(B) Guard post
flange in overlapping
joist position. Install
a stiffener on each
side.
7
7a
7a
7a
FIGURE 1 - ASSEMBLY
PAVERDECK
tm
EDECK625-S1200-54
Evolutiondeck Inc., 3422 Old Capitol Trail, Suite 700
Wilmington, DE 19808, 1-800-725-5228 mail@paverdeck.com
Specication, Page 2
Rev. 2016-05-01