Brochure
17
Dryer performance
DryerModels
Dewpoint
(Standard)
ISO8573-1:2010
Classification
(standard)
Dewpoint
(Option1)
ISO8573-1:2010
Classification
(Option1)
Dewpoint
(Option2)
ISO8573-1:2010
Classification
(Option2)
ºC ºF
ºC ºF ºC ºF
MXLE -40 -40 Class 2 -70 -100 Class 1 -20 -4 Class 3
PNEUDRI MXLE ADVANTAGE
Technical data
SingleBank
Model PipeSize
Flowrates
L/s m
3
/min m
3
/hr cfm
MXLE102C G 2 113 6.81 408 240
MXLE103C G 2 170 10.22 612 360
MXLE103 G 2 213 12.78 765 450
MXLE104 G 2 283 17.03 1020 600
MXLE105 G 2
1
/
2 354 21 1275 750
MXLE106 G 2
1
/
2 425 26 1530 900
MXLE107 G 2
1
/
2 496 30 1785 1050
MXLE108 G 2
1
/
2 567 34 2040 1200
Product Selection
Stated flows are for operation at 7 bar g (100 psi g) with reference to 20°C, 1 bar a, 0% relative water vapour pressure.
For flows at other pressures apply the correction factors shown.
* ISO8573-1 Classifications when used with included Parker domnick hunter OIL-X EVOLUTION pre / post filtration
Dryer
Models
Min
Operating
Pressure
Max
Operating
Pressure
Min
Operating
Temp
Max
Operating
Temp
Max
Ambient
Temp
Electricalsupply
(standard)
Electrical
supply
(optional)
Thread
Connections
Noise
Level
barg psig barg psig °C °F °C °F °C °F dB(A)
MXLE 5 58 13 190 5 41 50 122 55 131
380V - 420V 3PH 50Hz
440V - 480V 3PH 60Hz
N/A BSPP <75
Model MXLE102c MXLE103c MXLE103 MXLE104 MXLE105 MXLE106 MXLE107 MXLE108
Vacuum
PumpkW
50Hz 3 3 4 5.5 7.5 8 9.5 11
60Hz 3.6 3.6 4.8 6.6 9 9.6 11.4 13.2
Correction Factors
TemperatureCorrectionFactorCFT
MaximumInlet
Temperature
°C 25 30 35 40 45 50
°F 77 86 95 104 113 122
CFT 1.00 1.00 1.00 1.04 1.14 1.37
DewpointCorrectionFactorCFD
Option2 Standard Option1
Required
Dewpoint
PDP°C -20 -40 -70
PDP°F -4 -40 -100
CFD 0.91 1.00 1.43
PressureCorrectionFactorCFP
Minimum
InletPressure
barg 4 5 6 7 8 9 10 11 12 13
psig 58 73 87 100 116 131 145 160 174 189
CFP 1.60 1.33 1.14 1.00 0.89 0.80 0.73 0.67 0.62 0.57