Brochure
13
Dryer Performance
DryerModels
Dewpoint
(Standard)
ISO8573-1:2010
Classification
(standard)
Dewpoint
(Option1)
ISO8573-1:2010
Classification
(Option1)
Dewpoint
(Option2)
ISO8573-1:2010
Classification
(Option2)
ºC ºF ºC ºF ºC ºF
MX
-40 -40 Class 2 -70 -100 Class 1 -20 -4 Class 3
MXP* -40 -40 Class 2 -70 -100 Class 1 -20 -4 Class 3
PNEUDRI MX
Technical Data
Dryer
Models
Min
Operating
Pressure
Max
Operating
Pressure
Min
Operating
Temp
Max
Operating
Temp
Max
Ambient
Temp
Electricalsupply
(standard
Electrical
supply
(optional)
Thread
Connections
Noise
Level
barg psig barg psig °C °F °C °F °C °F dB(A)
MXS 4 58 13 190 5 41 50 122 55 131
85 - 265 V
1ph 50/60Hz
N/A
BSPP
or NPT
<75
MXA 4 58 13 190 5 41 50 122 55 131
85 - 265 V
1ph 50/60Hz
N/A
BSPP
or NPT
<75
MXP* 4 58 13 190 5 41 50 122 55 131 N/A N/A
BSPP
or NPT
<75
SingleBank
Model PipeSize
Flowrates
L/s m
3
/min m
3
/hr cfm
MX
102C
2" 113 6.81 408 240
MX 103C
2" 170 10.22 612 360
MX 103
2" 213 12.78 765 450
MX 104
2" 283 17.03 1020 600
MX 105
2
1
/
2" 354 21 1275 750
MX 106
2
1
/
2" 425 26 1530 900
MX 107
2
1
/
2" 496 30 1785 1050
MX 108
2
1
/
2" 567 34 2040 1200
Multi-Bank
2xMX 105
2
1
/
2" 708 43 2550 1500
2xMX 106
2
1
/
2" 850 51 3060 1800
2xMX 107
2
1
/
2" 992 60 3570 2100
2xMX 108
2
1
/
2" 1133 68 4080 2400
3xMX 106
2
1
/
2" 1275 77 4590 2700
3xMX 107
2
1
/
2" 1488 89 5355 3150
3xMX 108
G 2
1
/
2 1700 102 6120 3600
Product Selection
Stated flows are for operation at 7 bar g (100 psi g) with reference to 20°C, 1 bar a, 0% relative water vapour pressure.
For flows at other pressures apply the correction factors shown.
Controller Options
Controller
Options
Function
Poweron
Indication
Fault
Indication
DisplayFault
Condition
Values
Service
Interval
Indication
Service
Countdown
Timers
Comfigurable
Alarm
Settings
RemoteVolt
FreeAlarm
Contacts
Filter
Service
Timer
DDSEnergy
Management
System
SMART
• • • •
SMARTDDS
• • • • •
ADVANCED
• • • • • • • • •
*ATEX compliant option available.
For hazardous environments , a fully pneumatic ATEX compliant
version of PNEUDRI is available.
ATEX Directive 94/9/EC
Group II, Category 2GD, T6.