Brochure

Table Of Contents
Catalog CIC-2003-1/US
Pre-Filters, Oil Devices and Strainers
Parker Hannifin Corporation
Climate & Industrial Controls Group
Cleveland, OH
53
Pre-Filters,
Oil Devices
& Strainers
Technical Information
POS-321 Oil Separator, Oil Reservoirs, PS-033 Oil Strainer
POS-321 Oil Separator
The Parker oil separator removes oil from system
refrigerant by means of a highly efficient coalescing filter. The filter
is 98.5% efficient, filtering oil and particles down to 1/10 of a mi-
cron while leaving a trace amount of oil necessary for adequate
system lubrication. The separator is ideal for recovery and reclaim
operations.
Features and Benefits
3.6 ounces/108 ml capacity.
Standard 1/8" npt connection size.
1/4" or 3/8" flare or sweat connections optional.
For use with all CFC, HCFC and HFC refrigerants.
Design pressure of 500 psig / 3550 kPa / 35.5 bar.
U.L. listed SA5915.
Oil Reservoirs
Parker oil reservoirs are holding vessels for stand-by
oil necessary for the operation of a system.
Features and Benefits
Two or three sight glass ports for oil level
monitoring.
3/8" flare valve on the top and bottom shipped separately to
be adjusted per customer requirements. Allows isolation of
the reservoir for addition or removal of oil from the tank.
Vent port for connection to the suction line to
prevent pressure build up in the reservoir.
Available with mounting studs and brackets.
Other sizes available: 1/4 and 1/2 tons.
Model No.
Parker
Part No.
Total
Capacity
in Gallons
A
Capacity
Gallons
B
Capacity
Gallons
Length
Inches
POR-2 089351-00 2 3/4 3/4 18
POR-3 089379-00 3 3/4 3/4 23
POR-4 089350-00 3 3/4 1 1/2 36
Specifications
PS-033 Oil Strainer
Parker oil strainers removes contaminant from the oil line by
means of a 200 mesh filter screen.
Features and Benefits
Filtration area = 7.0 square inches.
3/8" SAE steel male flare connections.
U.L. listed.
Design pressure of 500 psig (3550 kPa).