Brochure

Table Of Contents
Flo-Con Pressure Regulators and Valves
Parker Hannifin Corporation
Climate & Industrial Controls Group
Cleveland, OH
343
Catalog CIC-2003-1/US
Flo-Con Pressure
Regulators
& Valves
NOTE: For SC valve suction capacity tables, please reference pages 290-297 of this catalog.
common commercial refrigerants along with certain
oils. The SC solenoid may be opened by means of a
manual opening stem for servicing or in case of an
electrical power failure.
The SC-II series of valves are manufactured with com-
pletely corrosion resistant materials including aluminum
bronze bodies and cartridge assemblies, and stainless
steel adapter bolts. Cartridges, and solenoids are inter-
changeable with the (S)PORT-II regulator line.
Variations: SC1/ SC-II Solenoids: Five port sizes, from
3/8" (9mm) through 1-3/8" (35mm). SC2 Solenoid: three
port sizes, from 1-5/8" (42mm) through 2-5/8" (66mm).
Installation: SC solenoid valves can be mounted either
in a vertical or horizontal line with the refrigerant flow in
the direction of the arrow on the body. These valves
may be soldered into the line without disassembly.
When brazing in line, typically a wet cloth wrapped
around the valve body is recommended to dissipate
heat. If a valve is disassembled prior to installation,
always have the correct gasket/ O-ring kit available
for reassembly. The internal cartridge-to-body O-ring
will need to be replaced prior to reassembly.
Electrical: SC commercial solenoid valves utilize a
molded water resistant Class “F” solenoid coil with an
open frame coil housing that meets NEMA 3R and 4
requirements. A class “H” DIN coil is also available with
certain voltages. Power consumption during normal
operation will be 10.2 watts or less.
All coils except for the 208/240V/60Hz version operate
with a 300 psi (20.7 bar) maximum opening pressure
differential (MOPD). The 208/240V/60Hz coil operates
with a 280 psi (19.3 bar) MOPD.
All coils are designed to operate with a line voltage
from 85% to 110% of rated coil voltage. Operating with
a line voltage above or below these limits may result in
coil burn out.
Ordering Guide: Specify valve type (SC1, SC-II or
SC2), port and connection size, coil voltage, and
frequency.
Technical Information SC Suction Solenoid Valves
SC1/SC2 Liquid Capacities in Evaporator Tons
Based on 100°F Condensing, 40°F Evaporator and no flashing through the valve for the pressure drop listed.
SC1/SC2 Liquid Capacities in Evaporator Kilowatts
Based on 37.7°C Condensing, 4.4°C Evaporator and no flashing through the valve for the pressure drop listed.
R22 R22 R134a R134a R404A R404A R507 R507
Port 2 psi 4 psi 2 psi 4 psi 2 psi 4 psi 2 psi 4 psi
Size pr drop pr drop pr drop pr drop pr drop pr drop pr drop pr drop
03 (3/8")69694646
05 (5/8") 14 20 13 19 9 12 9 13
07 (7/8") 22 31 21 29 14 19 14 20
09 (1-1/8") 35 50 33 47 22 31 23 32
11 (1-3/8") 49 69 46 65 30 43 32 45
13 (1-5/8") 78 110 73 104 48 68 50 71
17 (2-1/8") 117 165 110 156 72 102 76 107
21 (2-5/8") 156 220 147 207 96 136 101 143
R22 R22 R134a R134a R404A R404A R507 R507
Port 0.14 bar 0.27 bar 0.14 bar 0.27 bar 0.14 bar 0.27 bar 0.14 bar 0.27 bar
Size pr drop pr drop pr drop pr drop pr drop pr drop pr drop pr drop
03 (9mm) 23 32 21 30 14 20 15 21
05 (15mm) 50 71 47 67 31 44 32 46
07 (22mm) 78 110 73 103 48 68 50 71
09 (28mm) 123 174 116 164 76 107 80 113
11 (35mm) 172 243 162 229 106 150 111 157
13 (42mm) 274 387 258 365 169 239 177 251
17 (54mm) 411 581 387 547 253 358 266 376
21 (66mm) 548 775 516 729 338 477 354 501