Brochure

Table Of Contents
Catalog CIC-2003-1/US
Parker Hannifin Corporation
Climate & Industrial Controls Group
Cleveland, OH
167
Service
& Check
Valves
Thermostatic and Constant Pressure (Automatic) Expansion Valves
TXVs & AXVs
Valve Selection Procedure Thermostatic Expansion Valves
Selection of charge
Refer to pages 159 and 160 for a full explanation
of charge selection.
Select a charge which is best suited for the
application. Type W” charges are good all-purpose
charges, Z” charges are meant for low temperature
applications, and X” charges are for applications
requiring a pressure limit.
3. Choose the valve configuration which best suits
the application.
Select a model which best suits the needs of the
application based on fitting type, size, and orienta-
tion. Consider physical size and type of adjustment
available for each model.
Determine whether an external equalizer is
necessary. Combined pressure drops of the
distributor and evaporator which exceed 3 psi will
require an externally equalized valve for proper
operation.
Determine the full model number by combining
the information.
Nomenclature
(Example)
XX
Outlet
Fitting Size
and Type
1/2"
SAE
Inlet
Fitting Size
and Type
3/8"r
SAE
Maximum
Operating
Pressure
(MOP)
100
Valve Charge
See pages
134 and 157.
W
Z
X
X
Refrigerant
See pages
134 and
157.
V
Nominal
Capacity
in Tons
3
External
Equalizer
Omit for
Internal
Equalizer
E
External
Equalizer
Size and Type
1/4"
SAE/ODF
Valve
Model
G
Example of Valve Selection Procedure
1. Determine application information. The following
information was obtained from system design con-
straints. The example application is an R-22 freezer
which operates continuously at a temperature of 15°F.
The evaporator is rated at a 10° TD, therefore the
evaporator temperature is approximately 5°F. There are
no special pressure constraints on the compressor.
System refrigerant R-22
System capacity 13,600 BTU/hr (1.13 tons)
Evaporator temperature 5°F
Evaporator pressure 28 psig
Evaporator pressure losses
Distributor pressure drop 15 psi (estimated)
Evaporator pressure drop 6 psi (estimated)
Condenser pressure 225 psig
Liquid line pressure losses 4 psi (estimated)
Liquid temperature 90°F
Connections required 3/8" SAE liquid line con.
1/2" SAE evaporator con.
Valve adjustment
requirements Adjustable
Bypass bleed requirements None
2. Determine the required nominal capacity and
charge for the valve.
Selection of nominal capacity
Find the correct capacity
table Correct R-22 table on p. 154
Find the correct evaporator Refer to 0° evaporator
section (closest to 5°F
design temp.)
Determine available Condenser pressure 225 psig
pressure drop Evaporator pressure - 28 psig
Total pressure drop 197 psig
Subtract losses
Liquid line - 4 psi
Distributor - 15 psi
Evaporator - 6 psi
Net pressure drop 172 psi
Find correct pressure Refer to 175 psi pressure drop
drop column column
Find a capacity selection Find that there is a G(E)1
valve rated at 1.16 tons
Correct table capacity Refer to the liquid temperature
for liquid temperature table for R-22 and find a factor
correction of 1.08
1.16 tons x 1.08 = 1.23 tons
This valve will be operating at
92% capacity
Selection of charge
Select appropriate charge From evaporator temperature
range on page 135, choose VW
charge
3. Choose the valve configuration that's best for
the application
Select valve model Choose the G(E)1 for this
example.
Determine if there is an Pressure drop after the expan-
external eqaulizer sion valve is 11 psi (5 psi + 6
psi). It is necessary for the valve
to be externally equalized,
therefore the model number for
the valve will include the E”.
Determine the full model number; put the information together:
GE 1 VW 3/8"R SAE X 1/2" SAE X 1/4" SAE