Brochure

Table Of Contents
Parker Hannifin Corporation
Climate & Industrial Controls Group
Cleveland, OH
Catalog CIC-2003-1/US
Thermostatic and Constant Pressure (Automatic) Expansion Valves
164
General Information Thermostatic Expansion Valves
Off Cycle Unloading (Bleed)
Internal bleed orifices are used to equalize the high and
low side pressures during the off cycle so that low
starting torque compressors can start. Systems such
as air conditioners and heat pumps sometimes require
a TXV with internal bleed due to the frequent cycling
that occurs.
Consult the factory if a bypass bleed is required.
The required bleed size is a function of high and low
side system volumes, refrigerant charge, and pressure
difference across the valve prior to shutdown. These
variables affect the equalization time required by a time
delay device or thermostat reset. Bleed sizes are usu-
ally specified as a percentage of the nominal valve ca-
pacity and can range from 5% to 50%, although 15% to
30% is more commonly specified.
At the end of the valve model number, a letter B” fol-
lowed by digits indicates an internal bleed. These digits
represent the bleed capacity as a percentage of the
valves nominal capacity.
Example: SE5VX100B20 Bleed orifice 20% of 5 tons,
or 1 ton bypass bleed.
Because the internal bleed is an additional flow path in
the valve, adding a bleed will increase the capacity of
the valve. Thus, a 5 ton valve with a 20% bleed is actu-
ally capable of 6 tons. However, intentionally adding an
internal bleed to increase the capacity of a valve is not
recommended.
Bulb Location and Installation
Since the control response of the bulb is crucial for sat-
isfactory operation, care should be taken in its mount-
ing and positioning.
Always make sure the suction line is cleaned before
clamping the bulb in place.
On lines that are 1/2" O.D. or smaller, the bulb may
be installed on top of the line or side mounted (pref-
erably at the 3 oclock position).
On lines that are 7/8" O.D. or larger, the remote bulb
should be installed at 45° or at approximately the 4
or 8 oclock position.
Never mount a bulb on the bottom of suction lines
because a mixture of refrigerant and oil may be
present at that point, especially on smaller lines.
It is good practice to insulate the bulb regardless of
the refrigerant type. This ensures that the bulb will
only respond to the suction gas temperature and will
not be affected by condensation, ice formation or
ambient temperatures.
Avoid mounting the bulb on vertical lines or close to
reversing valves.
The bulb should always be mounted between the
evaporator outlet and the external equalizer connec-
tion and should be as close to the evaporator outlet
as possible (generally 3 to 6 inches).
On systems that have multiple evaporators, the bulb
must be mounted on the suction line of the evapora-
tor which it controls. Do not mount the bulb on the
common suction line.
Install traps on vertical risers. (See the illustration
below.)
1/2" & smaller
suction line
5/8" & larger
suction line
on smaller lines,
bulb may be mounted
on top
do not mount
bulb on bottom
of line
Installation of Traps