User's Manual
OMNSMK1-TI00
PRINTED IN CANADA 03/2003
English
Installation
The OMN-SMK1 should be mounted on the ceiling (or wall if necessary) in
accordance with the NFPA Standard 74 (National Protection Association,
Batterymarch Park, Quincy, MA 02169) outlined on reverse. The OMN-SMK1 is
a wireless detector designed to work with the OMN-RCV3 wireless receiver and
cannot be linked to other smoke detectors.
The detector will not warn people who are deaf or hard of
hearing. Special-purpose detectors with light or vibrating
devices should be installed.
For optimal detection, the unit should be mounted as close to the center of the
ceiling as possible. Always test the unit before it has been powered and after
installation as outlined in “Testing the Smoke Detector”. After selecting the
detector's location, drill or punch out holes for the screws as shown in Figure 2
on reverse and follow the steps outlined below.
Mounting the Detector
1. Use two of the eight keyhole slots to mark where you will drill the
mounting holes and insert the plastic wall plugs.
2. Align the mounting bracket to the wall plugs and partially insert the
screws.
3. Once the mounting bracket is positioned, secure it and tighten both
screws.
4. Join the detector to the mounting bracket, by aligning the lock tab to
the preferred lock slot (Figure 2 on reverse), then turn
counter-clockwise to lock detector into place.
The mounting bracket comes with two “tamper proof” threads. Remove
these threads in order to change the battery or if you wish to mount the
detector to an alternative location.
Unmounting the Detector
Remove the detector from the mounting bracket by gently pulling the
detector, then turning clockwise as shown in Figure 2 on reverse.
Alternative Locations
If a ceiling installation is not possible, the following alternative locations
are recommended:
• Ceiling mount no closer than 10cm (4”) from any wall or corner as
shown in Figure 6 on reverse.
• Wall mount (permitted by your local and state codes) between 10 and
15cm (4 to 6”) from the ceiling as shown in Figure 6 on reverse.
• For sloped or peaked ceiling, try to mount the detector 1m (3.2ft)
measured horizontally from the highest point of the ceiling as shown in
Figure 6 on reverse.
The OMN-SMK1 is designed to give early warning of developing
fires by sensing smoke. It will not sense gas, heat and flame
sources.
Residential Installations
The detector is designed for use inside a single residential unit such as a
family home or apartment. For complete coverage in residential units,
smoke detectors should be installed in the following locations:
• In any hallway outside bedroom areas. Additional detectors should be
installed for every bedroom area as shown in Figure 3 on reverse.
• On every floor of a multi-floor home or apartment as shown in Figure 5
on reverse.
• At both ends of a bedroom hallway if the hallway is more than 12m
(40ft) long.
• At the bottom of a basement stairwell.
• At the top of the first to second floor stairwell and subsequent stairwells
in multi-floored residential units.
Detectors should be installed as close to the center of the ceiling
as possible. If this is not practical refer to Figure 6 on reverse for
alternative locations.
Non-residential Installations
The detector is not intended for non-residential installations. The
following locations are not recommended:
• Warehouses.
• Industrial or commercial buildings.
• Places where people may live and work such as motels, hotels,
dormitories, nursing homes, group homes even if they were previously
used as family homes.
• Special non-residential buildings that require specific fire/smoke
detection systems.
• Lobbies or hallways or basements of multi-family buildings.
Please refer NFPA 101, the Life Safety Code, NFPA71, 72A, 72B,
72C, 72D and 72E for smoke detector requirements for fire
protection in buildings not defined as “households”.
Detection Parameters
Installation in the following areas may cause false alarms or impede with
the detector’s ability to provide sufficient early warning. Avoid the
following areas:
• Dusty areas such as a garage or attic.
• Areas where the temperature may fall below 4ºc (40ºF) or rise above
38ºC (100ºF).
• Near fluorescent electrical lights. If this cannot be avoided, ensure a
minimum installation distance of at least 1.5m (5ft).
• Areas with poor ventilation or obstructions that may prevent smoke from
reaching the detector. These can be the top of a peaked (sloped) roof or
ceiling (Figure 5 on reverse) and a partially or completely closed
bedroom door.
• Near furnaces or hot water heaters.
• Humid or damp areas such as a washroom or shower. If this cannot be
avoided, ensure a minimum installation distance of at least 3m (10ft).
• Near ventilated areas that may draw smoke away from the detector.
• Insect-infested areas.
• Areas less than 6m (20ft) away from the kitchen or cooking appliances.
Never remove the batteries to stop a false alarm. Allow
sufficient ventilation to reach the detector until the false
alarm stops. If false alarms persist, clean out the detector.
Powering the Detector
Insert the battery in the compartment located under the detector. You can insert
an optional screw to secure the compartment door. Align the terminals on the
end of the (alkaline) battery to those of the detector (Figure 1 on reverse). When
the detector first makes contact with the battery, the LED will flicker and the horn
will sound for one second. This means that the battery is properly connected.
Close the cover and hold down the test button for five seconds. The horn will
emit a loud pulsating sound to indicate that the unit is working.
LED Smoke Signal Indication
Once smoke is detected, the OMN-SMK1 will emit three continuous alarms,
pause and repeat this alarm pattern until the smoke condition has stopped. In
addition, during an alarm, the red LED will flicker rapidly.
Upon detection of an alarm condition (smoke) the OMN-SMK1 will transmit the
alarm signal every 30 seconds to the OMN-RCV3 receiver until the condition
stops.
Once the alarm condition has stopped, the detector will wait 5 seconds then
transmit a restore signal to the receiver. The restore signal is transmitted only
once to the receiver after an alarm condition has stopped.
Testing the Smoke Detector
Test the detector by pushing firmly on the test button with your finger until the
horn activates. Horn activation may take up to 20 seconds to occur. If the
detector does not emit an alarm, verify that the battery is connected or that any
old batteries have been replaced then re-test the unit. If the detector does not
respond, contact your distributor.
Do not use an open flame to test the detector.
Low Battery
The OMN-SMK1 transmits a supervision (self-test) signal to the receiver every
12 hours. If the detector experiences a low battery condition, it will wait 5 minutes
then transmit a low battery signal to the receiver. The detector will continue to
transmit a low battery signal every 12 hours until the battery is replaced.
Taking Care of Your Detector
Your smoke detector requires little maintenance. To optimize your detector’s
performance, the following guidelines are recommended.
• Test the detector once a week.
• Replace the battery once a year or upon hearing the “weak battery” signal.
• Use only 9V alkaline batteries. Carbon zinc batteries are not acceptable.
• Open the cover and remove any accumulated dust at least once a year. This
includes the detector’s sensing chamber as shown in Figure 1 on reverse.
Instructions
Instrucciones
Photoelectric Wireless
Smoke Detector
OMN-SMK1