Installation Instructions

Table Of Contents
26 Reference & Installation Manual
8.3.1 Tamper Bypass Options
Section [132]: Zone Options
Option [3] OFF = Will generate a tamper if detected on a bypassed zone (default)
Option [3] ON = Tampers on bypassed zones will be ignored
With option [3] on, the Tamper Recognition feature follows the zone bypass definition. This means the control panel
will ignore any tampers detected on a bypassed zone. With option [3] off, Tamper Recognition ignores the bypass
definition. This means the control panel will generate an incident as per Tamper Recognition settings if a tamper or
wire fault occurs on a bypassed zone.
8.4 Keypad Panic Options
Section [128]: General Options
Option [1] OFF = Emergency Panic Disabled (default)
Option [1] ON = Emergency Panic Enabled
Pressing the [1] and [3] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [4].
Option [2] OFF = Auxiliary Panic Disabled (default)
Option [2] ON = Auxiliary Panic Enabled
Pressing the [4] and [6] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [5].
Option [3] OFF = Fire Panic Disabled (default)
Option [3] ON = Fire Panic Enabled
Pressing the [7] and [9] keys simultaneously on the keypad for 2 seconds will generate a silent or audible alarm as defined by
option [6].
Option [4] OFF = Emergency Panic is Silent (default)
Option [4] ON = Emergency Panic is Audible
Option [5] OFF = Auxiliary Panic is Silent (default)
Option [5] ON = Auxiliary Panic is Audible
Option [6] OFF = Fire Panic is Silent (default)
Option [6] ON = Fire Panic is Pulsed
Silent alarm
:
The control panel emits a confirmation beep and transmits the appropriate Panic report code if programmed in section [195]. The
control panel will not enable the keypad buzzers or the control panel’s BELL output (no audible alarm).
Audible alarm
:
Same as silent alarm, except the keypad buzzers and the BELL output will activate until a user cancels the alarm (disarms) with a
valid user access code or when the Bell Cut-Off Timer elapses (see page 25).
Fire (pulsed) alarm
:
Same as audible operation, except that the
BELL output will be pulsed as shown in Figure 11 on page 15.
Whether the system is partitioned or not, the control panel will report all panic alarms to partition 1.
8.5 Panic Lockout Timer
Section [094]
When a panic alarm is activated, the control panel can ignore the disarm signal from a remote control for a specified period. This
prevents an aggressor from disarming the system by remote control during a panic situation. In section [094] enter a 3-digit value
(000 to 255, 000 = disabled) representing the number of seconds that the remote controls will be locked out of the system.