Installation Instructions

Table Of Contents
16 Reference & Installation Manual
5.9 Zone Options
As demonstrated in Figure 10 on page 13, sections [001] to [015] represent zones 1 through 15 respectively. After entering the first
two digits, select one or more of the following Zone Options by using the Multiple Feature Select Programming Method (see page 7):
5.9.1 Auto Zone Shutdown
Sections [001] to [015] = Zones 1 to 15
Option [1] OFF = Auto Zone Shutdown Disabled
Option [1] ON = Auto Zone Shutdown Enabled for
selected zone (default)
If, in a single armed period, the number of alarms generated by a zone with the Auto Zone Shutdown option enabled
exceeds the number defined by the Auto Zone Shutdown Counter, the control panel will no longer generate an alarm
for that zone. To program the Auto Zone Shutdown Counter, key in the desired limit (000=Disabled, 001 to 015, Default
= 5) into section [089]. The Auto Zone Shutdown Counter resets every time the partition that is assigned to the
corresponding zone is armed.
5.9.2 Bypass Zones
Sections [001] to [015] = Zones 1 to 15
Option [2] OFF = Bypass Zone Disabled
Option [2] ON = Selected Zone is Bypass Enabled (default)
When a user utilizes the Bypass Programming feature (see page 44), only zones with the Bypass option enabled can
be programmed as bypassed.
Do not program a fire zone with the Bypass option, as the control panel will never bypass fire zones.
5.9.3 Stay Zones
Sections [001] to [015]: Zones 1 to 15
Option [3] OFF = Stay Zone Disabled (default)
Option [3] ON = Selected Zone is Stay Enabled
Zones with the Stay option enabled will be bypassed when the system is Stay Armed (see page 44).
Do not program a fire zone with the Stay option, as the control panel will never bypass fire zones when
Stay arming.
5.9.4 Alarm Types
Sections [001] to [015]: Zones 1 to 15
[4] OFF / [5] OFF: Audible Steady (default)
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 28) and provides a steady output for any bells or sirens connected to the control panel’s bell output.
[4] OFF / [5] ON: Audible Pulsed Alarm
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 28) and provides a pulsed output (see Figure 11 on page 15) for any bells or sirens connected to the
control panel’s bell output.
[4] ON / [5] OFF: Silent Alarm
When the conditions for an alarm are met, the control panel can transmit the appropriate Zone Alarm report code (see
page 28) and will not activate the control panel’s bell output. The appropriate
ARM or STATUS LED on the keypads will
flash to indicate an alarm and the user will still have to disarm the system.
[4] ON / [5] ON: Report Only
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 28). The system will not have to be disarmed.
5.9.5 Intellizone
Sections [001] to [015]: Zones 1 to 15
Option [6] OFF = Intellizone Disabled (default)
Option [6] ON = Intellizone Enabled for Selected Zone
This feature reduces the possibility of false alarms. When a zone with the Intellizone option opens, the panel does not
immediately generate an alarm. First it triggers the Intellizone Delay Timer. To program the Intellizone Delay Timer, key
in the desired 3-digit value (010 to 255 seconds, Default = 48 seconds) into section [084]. If any of the following
conditions occur during this period, the panel will generate an alarm:
During the Intellizone Delay, a second zone has caused an alarm.
During the Intellizone Delay, the zone in alarm has restored (closed) and re-occurred (opened).
The zone in alarm remains open for the entire Intellizone Delay.