Installation Instructions

Table Of Contents
Spectra 1759MG 13
5.3 Reassign Zones to Expansion Inputs
Section [126]: General Options
Option [8] OFF = Reassign Zones to Expansion Inputs Disabled (default)
Option [8] ON = Reassign Zones to Expansion Inputs Enabled
In installations that require using mostly the expansion inputs, such as using wireless zones, 10-Zone LED keypads may be
unable to display some of the zones. The Reassign Zones to Expansion Inputs feature changes the zone numbering to increase
the number of expansion inputs that are displayed on 10-Zone LED keypads. Combine with the Reassign Keypad Zone 2 feature
(refer to Reassign Keypad Zone 2 on page 12) to increase the number of displayable expansion inputs. See Table 4 on page 12
for the Zone Recognition.
5.4 Zone Programming
After connecting a hardwired detection device to one of the control panel's or zone expansion bus module’s input terminals or
after setting up any wireless transmitters, define the associated zone's parameters. The zone parameters define the type of zone,
the zone's partition assignment and how the control panel will react when an alarm condition occurs on that zone. These zone
parameters are programmed into one section as detailed in Figure 10 on page 13.
See Table 4 on page 12 for the Zone Number Recognition.
Only the control panel’s on-board inputs can be defined as a fire, delayed fire or a keyswitch zone. The on-board
zones are zones 01 to 05.
Figure 10: Spectra Zone Programming
5.5 Zone Definitions
As demonstrated in Figure 10, sections [001] to [015] represent zones 1 through 15 respectively, where the first digit in each of
these sections represents the zone's definition. Also, refer to Zone Speed on page 17. To disable a zone, clear the contents of the
section corresponding to the desired zone by pressing the [
FORCE] key 3 times and pressing [ENTER]. There are 9 available Zone
Definitions, which are described as follows.
Zone Definitions
1 - Entry Delay 1
2 - Entry Delay 2
3 - Follow
4 - Instant
5 - 24Hr Burglary
6 - 24Hr Buzzer
Additional definitions for
on-board terminals:
7 - Keyswitch
8 - 24Hr Fire
9 - 24Hr Delayed Fire
Press the
[
ENTER] key
Enter the
[
INSTALLER CODE]
Key in 3-digit
[
SECTION]
Zone Definition
First Digit
Zone Partition
Assignment
Second Digit
Zone Options
Feature Select
Press [ENTER]
[001] = Zone 1 [009] = Zone 9
[002] = Zone 2 [010] = Zone 10
[003] = Zone 3 [011] = Zone 11
[004] = Zone 4 [012] = Zone 12
[005] = Zone 5 [013] = Zone 13
[006] = Zone 6 [014] = Zone 14
[007] = Zone 7 [015] = Zone 15
[008] = Zone 8
Zone Partition Assignment
1 - Zone Assigned to Partition 1
2 - Zone Assigned to Partition 2
3 - Zone Assigned to both Partitions
Zone Options
[1] Auto Zone Shutdown Enabled
[2] Bypass Enabled
[3] Stay Zone
[4] [5] Zone Alarm Type
OFF OFF Audible Alarm (steady)
OFF ON Audible Alarm (pulsed)
ON OFF Silent Alarm
ON ON Generates only a report
[6] Intellizone
[7] Delay alarm transmission
[8] Force Zone
Keyswitch Options
[1] OFF= Maintained
ON = Momentary
[2] OFF = Regular Arm
ON = Stay Arm
Keypads beep twice
Select
one
Select
one