User's Manual
Table Of Contents
- Table of Contents
- Part 1: Introduction
- Part 2: Installation
- Part 3: Programming Methods
- Part 5: Zone Programming
- Part 7: Arming and Disarming Options
- 7.1 Switch To Stay Arming
- 7.2 Stay Arming with Delay
- 7.3 Regular Arming switches to Force Arming (Not to be used with UL Installations)
- 7.4 Restrict Arming On Battery Fail
- 7.5 Restrict Arming On Tamper Failure
- 7.6 Timed Auto-Arming
- 7.7 No Movement Auto-Arming
- 7.8 Auto-Arming Options (Not to be used with UL installations)
- 7.9 One-Touch Arming (Not to be used with UL installations)
- 7.10 Exit Delay
- 7.11 Bell Squawk On Arm/Disarm With Keypad
- 7.12 Bell Squawk On Arm/disarm with Remote Control
- 7.13 No Exit Delay When Arming with Remote Control
- 7.14 No Exit Delay Beeps and No Bell Squawk When Stay Arming
- Part 8: Alarm Options
- Part 9: Reporting and Dialer settings
- 9.1 Reporting/Dialer (Enable/Disable)
- 9.2 Report Codes
- 9.3 Central Station Telephone Numbers
- 9.4 Partition Account Numbers
- 9.5 Reporting Formats
- 9.6 Pager Delay
- 9.7 Event Call Direction
- 9.8 Dialing Method
- 9.9 Pulse Ratio
- 9.10 Bell on Communication Failure
- 9.11 Dial Tone Delay
- 9.12 Maximum Dialing Attempts
- 9.13 Delay Between Dialing Attempts
- 9.14 Alternate Dial Option
- 9.15 Recent Close Delay
- 9.16 Auto Test Report
- 9.17 Power Failure Report Delay
- 9.18 Disarm Reporting Options
- 9.19 Zone Restore Report Options
- 9.20 Telephone Line Monitoring (TLM)
- Part 10: Programmable Outputs
- Part 11: System Settings
- 11.1 Hardware Reset
- 11.2 Installer Lock
- 11.3 Keypad Lockout Feature
- 11.4 Battery Charge Current
- 11.5 Partitioning
- 11.6 System Real-Time Clock
- 11.7 Clock Adjust
- 11.8 Keypad Tamper Supervision
- 11.9 Keypad Audible Trouble Warning
- 11.10 Confidential Mode
- 11.11 Installer Quick Functions Keys
- 11.12 PGM Modules Supervision
- 11.13 Printer Module Supervision
- 11.14 Zone Expansion Bus Module Supervision
- 11.15 Wireless Transmitter Low Battery Supervision
- 11.16 Wireless Transmitter Supervision Options
- 11.17 ReProgram All Expansion Modules
- Part 12: Settings for WinLoad Software
- Part 13: User Operation
- 13.1 Trouble Display
- 13.2 Programming Access Codes
- 13.3 Disarming & Deactivating an Alarm
- 13.4 Regular Arming
- 13.5 Stay Arming
- 13.6 Instant Arming
- 13.7 Force Arming (Not to be used with UL Installations)
- 13.8 Manual Bypass Programming
- 13.9 One-Touch Arming
- 13.10 Keyswitch Arming
- 13.11 Panic Alarms
- 13.12 Auto-Arming (Not to be used with UL installations)
- 13.13 Alarm Memory Display
- 13.14 Programming Chime Zones
- 13.15 Keypad Muting (Not to be used with UL installations)
- 13.16 Keypad Backlight (1686H and 1686V only)
- FCC WARNINGS
- Index
PART 2: INSTALLATION
2.1 LOCATION AND MOUNTING
Before mounting the cabinet, push the five white nylon mounting studs into the back of the cabinet. Pull all cables into the cabinet
and prepare them for connection before mounting the circuit board into the back of the cabinet. Select a centralized installation
site on the main floor that isn't easily accessible to intruders and leave at least 2in. (5cm) around the panel box to permit
adequate ventilation and heat dissipation. The installation site should be dry and close to an AC source, ground connection and
telephone line connection. Avoid installation near or in the path of strong RF fields (i.e. neon lights, computers), on or near metal
objects, circuit breaker boxes, air conditioners and heater ducts since they may cause interference and reduce sensitivity. Avoid
installing the 1759EX in the basement.
2.2 EARTH GROUND
Connect the zone and dialer ground terminals from the control panel to the metallic enclosure and cold water pipe or grounding
rod as per local electrical codes.
For maximum lightning protection, use separate earth grounds for the zone and dialer grounds as shown in
Figure 2.2 on page 5. For UL installations, the metallic enclosure must be grounded to the cold water pipe.
2.3 AC POWER
Do not use any switch-controlled outlets to power the transformer. Connect the transformer as shown in Figure 2.1 on page 4.
Use Table 1 to determine the required transformer.
2.4 BACKUP BATTERY
To provide power during a power loss, connect a 12Vdc 4Ah rechargeable acid/lead or gel cell backup battery as shown in Figure
2.1 on page 4. Use a 7Ah battery to comply with UL fire requirements. Connect the backup battery after applying AC power.
When installing verify proper polarity as reversed connections will blow the battery fuse. Also, refer to Battery Charge Current on
page 39.
2.4.1 BATTERY TEST
If the battery is disconnected or if the battery fuse is blown, a No/Low Battery failure will appear in the keypads’ Trouble Display
(see page 45). This trouble will also appear if the battery’s capacity is too low or if the voltage drops to 10.5 volts or lower while
the control panel is running on the backup battery. At 8.5 volts or lower, the panel shuts down and all outputs close.
Figure 2.1: AC Power and Backup Battery Connections
Table 1:
Transformer Requirements Table
Transformer: Amseco XP-1620 16VAC 20VA
(not verified by UL)
UL: Basler Electric BE156240CAA007
16.5VAC 40VA
Spectra DC Power Supply rated at: 1.2A 1.5A
Auxiliary Supply can provide a maximum of: typ: 600mA, max: 700mA typ: 600mA, max: 700mA
Do not exceed 200mA for UL installations
Acceptable Battery Charge Currents 350mA 350mA/700mA