User's Manual
Table Of Contents
- Table of Contents
- Part 1: Introduction
- Part 2: Installation
- Part 3: Programming Methods
- Part 5: Zone Programming
- Part 7: Arming and Disarming Options
- 7.1 Switch To Stay Arming
- 7.2 Stay Arming with Delay
- 7.3 Regular Arming switches to Force Arming (Not to be used with UL Installations)
- 7.4 Restrict Arming On Battery Fail
- 7.5 Restrict Arming On Tamper Failure
- 7.6 Timed Auto-Arming
- 7.7 No Movement Auto-Arming
- 7.8 Auto-Arming Options (Not to be used with UL installations)
- 7.9 One-Touch Arming (Not to be used with UL installations)
- 7.10 Exit Delay
- 7.11 Bell Squawk On Arm/Disarm With Keypad
- 7.12 Bell Squawk On Arm/disarm with Remote Control
- 7.13 No Exit Delay When Arming with Remote Control
- 7.14 No Exit Delay Beeps and No Bell Squawk When Stay Arming
- Part 8: Alarm Options
- Part 9: Reporting and Dialer settings
- 9.1 Reporting/Dialer (Enable/Disable)
- 9.2 Report Codes
- 9.3 Central Station Telephone Numbers
- 9.4 Partition Account Numbers
- 9.5 Reporting Formats
- 9.6 Pager Delay
- 9.7 Event Call Direction
- 9.8 Dialing Method
- 9.9 Pulse Ratio
- 9.10 Bell on Communication Failure
- 9.11 Dial Tone Delay
- 9.12 Maximum Dialing Attempts
- 9.13 Delay Between Dialing Attempts
- 9.14 Alternate Dial Option
- 9.15 Recent Close Delay
- 9.16 Auto Test Report
- 9.17 Power Failure Report Delay
- 9.18 Disarm Reporting Options
- 9.19 Zone Restore Report Options
- 9.20 Telephone Line Monitoring (TLM)
- Part 10: Programmable Outputs
- Part 11: System Settings
- 11.1 Hardware Reset
- 11.2 Installer Lock
- 11.3 Keypad Lockout Feature
- 11.4 Battery Charge Current
- 11.5 Partitioning
- 11.6 System Real-Time Clock
- 11.7 Clock Adjust
- 11.8 Keypad Tamper Supervision
- 11.9 Keypad Audible Trouble Warning
- 11.10 Confidential Mode
- 11.11 Installer Quick Functions Keys
- 11.12 PGM Modules Supervision
- 11.13 Printer Module Supervision
- 11.14 Zone Expansion Bus Module Supervision
- 11.15 Wireless Transmitter Low Battery Supervision
- 11.16 Wireless Transmitter Supervision Options
- 11.17 ReProgram All Expansion Modules
- Part 12: Settings for WinLoad Software
- Part 13: User Operation
- 13.1 Trouble Display
- 13.2 Programming Access Codes
- 13.3 Disarming & Deactivating an Alarm
- 13.4 Regular Arming
- 13.5 Stay Arming
- 13.6 Instant Arming
- 13.7 Force Arming (Not to be used with UL Installations)
- 13.8 Manual Bypass Programming
- 13.9 One-Touch Arming
- 13.10 Keyswitch Arming
- 13.11 Panic Alarms
- 13.12 Auto-Arming (Not to be used with UL installations)
- 13.13 Alarm Memory Display
- 13.14 Programming Chime Zones
- 13.15 Keypad Muting (Not to be used with UL installations)
- 13.16 Keypad Backlight (1686H and 1686V only)
- FCC WARNINGS
- Index
5.7 ZONE PARTITION ASSIGNMENT
Sections [001] to [015]: Zones 1 to 15
The control panel provides the option of partitioning the security system
into two completely independent systems. As demonstrated in Figure 5-1
on page 16, sections [001] to [015] represent zones 1 through 15
respectively, where the second digit in each of these sections represents
the zone's partition assignment. The zone is assigned to Partition 1 if
second digit = 1, Partition 2 if second digit = 2, or both partitions is
second digit = 3. For details on Partitioning, refer to page 39.
5.8 ZONE OPTIONS
As demonstrated in Figure 5.1, sections [001] to [015] represent zones 1
through 15 respectively. After entering the first two digits, select one or
more of the following Zone Options by using the Multiple Feature Select
Programming Method (see page 9):
5.8.1 AUTO ZONE SHUTDOWN
Sections [001] to [015] = Zones 1 to 15
Option [1] OFF = Auto Zone Shutdown Disabled
Option [1] ON = Auto Zone Shutdown Enabled for
selected zone (default)
If, in a single armed period, the number of alarms generated by
a zone with the Auto Zone Shutdown option enabled exceeds
the number defined by the Auto Zone Shutdown Counter, the
control panel will no longer generate an alarm for that zone. To
program the Auto Zone Shutdown Counter, key in the desired
limit (000=Disabled, 001 to 015, Default = 5) into section [089].
The Auto Zone Shutdown Counter resets every time the
system is armed.
5.8.2 BYPASS ZONES
Sections [001] to [015] = Zones 1 to 15
Option [2] OFF = Bypass Zone Disabled
Option [2] ON = Selected Zone is Bypass Enabled (default)
When a user, utilizes the Bypass Programming feature (see page 47), only zones with the Bypass option enabled can
be programmed as bypassed.
Do not program a Fire Zone with the Bypass option, as the control panel will never bypass Fire Zones.
5.8.3 STAY ZONES
Sections [001] to [015]: Zones 1 to 15
Option [3] OFF = Stay Zone Disabled (default)
Option [3] ON = Selected Zone is Stay Enabled
Zones with the Stay option enabled will be bypassed when the system is Stay Armed (see page 47).
Do not program a Fire Zone with the Stay option, as the control panel will never bypass Fire Zones
when Stay Arming.
5.8.4 ALARM TYPES
Sections [001] to [015]: Zones 1 to 15
[4] OFF / [5] OFF: Audible Steady (default)
When the conditions for an alarm have been met, the control panel can transmit the appropriate Zone Alarm report
code (see page 31) and provides a steady output for any bells or sirens connected to the control panel’s bell output.
Figure 5.2: Bell Output During Fire Alarm Figure 5.3: Delayed 24Hr. Fire Zone