Technical Bulletin

VeriSafe
Absence of Voltage Tester
7
Applications
Electrical System For use in 1 and 3-phase AC and DC systems
Voltage Detection Range Up to 600V AC (50/60Hz), 600V DC; Rated tolerance +10%
Absence of Voltage Threshold 3 V
Overvoltage Category III (600 V) CAT IV 300V
Degree of Protection* Indicator Module: For Flat Surface Mounting in a TYPE (UL, NEMA and CSA) 1, 12, 13, 4, 4X, IP66, or
IP67 Enclosure
Isolation Module: Open Type, IP20
Environment
Operating Temperature (with
included Tadiran TL-5903)
0°C to + 60°C (32°F to 140°F)
Operating Temperature (with Titus
ER14505M) (VS-AVT-BATTERY)
-25°C to + 60°C (-13°F to 140°F)
Storage Temperature -45°C to + 85°C (-49°F to +185°F)
Humidity 5 to 90% non-condensing; Rated 80% at 40°C, decreasing linearly to 50% at 60°C
Pollution Degree 3
Altitude Up to 5000 meters (3.11 miles)
Battery
Type Industrial 3.6V Lithium AA, see table in Maintenance section of installation guide for compatible batteries.
Standards apply to VS-AVT and VS-AVT2
UL 1436 Standard for outlet circuit testers and similar indicating devices
CAN/CSA-C22.2 No. 160 Voltage and Polarity Testers
IEC/UL/CSA C22.2 No. 61010-1 Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 1:
General Requirements
IEC/UL/CSA C22.2 No. 61010-2-
030
Safety requirements for electrical equipment for measurement, control, and laboratory use – Part 2-030:
Particular requirements for testing and measuring circuits
UL 508 & CSA-C22.2 No. 14 Industrial control equipment
IEC 61508-1, -2, and -3 {SIL 3
Rating}
Safety of Electrical/Electronic/programmable Electronic safety-related security systems –
Part 1 General Requirements
Part 2 Requirements for Electrical/Electronic/Programmable safety related systems
Part 3 Software Requirements
FCC - CFR 47 Part 15 Subpart B Radio frequency devices
IEC 61326-1, -3-1, -3-1: corr 1
EN 61326-1, -3-1
Electrical equipment for measurement, control and laboratory use-EMC requirements – Part 1
Part 3-1: Immunity requirements for safety-related systems and for equipment intended to perform
safety-related functions (functional safety) – General industrial applications including corrigendum 1
EN 55011, CISPR 11 Industrial, scientic and medical equipment – Radio-frequency disturbance characteristics – Limits and
methods of measurement
IEC/EN61000-3-2
IEC/EN61000-3-3
Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for harmonic current emissions (equipment
input current 16 A per phase)
EN 61000-6-2 Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity for industrial environments
AS/NZS CISPR 11 Australian/New Zealand Standard – Industrial, scientic and medical equipment – Radio-frequency
disturbance characteristics – Limits and methods of measurement
CAN - ICES-001 Industrial, Scientic and Medical (ISM) radio frequency generators.
CE Conformity Marking for European Economic Area
RoHS Restriction of hazardous substances
Standards apply to VS-AVT2 only
ISA 12.12.01 Nonincendive Electrical Equipment rated for Class I, Division 2 area classication, Groups A, B, C, D, and
temperature classication T3.
CSA C22.2 NO. 213 Nonincendive Electrical Equipment rated for Class I, Zone 2 area classication, Groups IIA, IIB, and IIC,
and temperature classication T3.
*Degree of protection specified is related to the Indicator Module only. To meet the TYPE (UL, NEMA and CSA) 1, 12, 13, 4 or 4X requirements,
mount on a flat surface of an enclosure meeting the appropriate UL TYPE or NEMA rating. Verify that the seal and o-rings are clean to ensure
proper sealing.
Technical Specifications
DIN rail
mounting clip