Busbars
Typical Installation
Considerations
• Sensor leads may be terminated
using barrel post lug, ring terminals,
bolted connections or other
compliant methods
• Carefully route and secure sensor
leads
• Consult manufacturer before making
modifications to busbars
• AVT sensor leads must have ferrules
(or terminals) applied at all
termination points
SCCR Impact
No Impact
Limitations
• If extending the sensor leads, the
total length of the sensor leads plus
the sensor lead extensions must be
less than 10ft from the isolation
module to the connection point on
the power conductor (to comply with
NEC tap rule)
• Sensor leads must not be terminated
under the same screw.