3) Common Methods for Terminating VeriSafe AVT Sensor Leads
This section describes some of the common methods used to terminate VeriSafe AVT sensor leads. Other
methods or combinations of these methods can be used as long as they comply with the
VeriSafe AVT
Instruction Manual and local installation codes and standards.
VeriSafe Insulation Piercing Connector
Typical Installation
Considerations
• Single connector is used to terminate two sensor
leads, allowing for a smaller connector footprint
and faster installation
• Insulation piercing connectors do not compromise
the integrity of the conductor
• AVT sensor leads must have ferrules applied at all
termination points
SCCR Impact
No Impact
Limitations
• If extending the sensor leads, the total length of the
sensor leads plus the sensor lead extensions must
be less than 10ft from the isolation module to the
connection point on the power conductor (to
comply with NEC tap rule)
VeriSafe Insulation Piercing Connector Kit
Each kit includes three connectors & ferrules to install one AVT
Part Number
Product Description
VS-CKP14-6
VeriSafe AVT Insulation Piercing Connection Kit for
tapping 14 to 6 AWG conductors.
VS-CKP4-000
VeriSafe AVT Insulation Connection Kit for Tapping 4 to
3/0 AWG conductors.