Other Examples
Siemens control tap (as shown Siemens part number is
3VA91430JH12) that is compatible with one bolt
connection yet allows for two separate “ports” separated
by a set screw.
Sensor leads are not tied together and separated by the
terminal screw
AVT sensor leads must have ferrules applied
\
Utilize dual hole lugs. Connect sensor leads with ring
terminals.
Each AVT sensor lead must be terminated at a separate
point.
Panduit product series dual hole lug LCC” – link
to
catalog cut sheet
Rockwell terminal adapters (SKU as shown is 1494U-
ALT31) with a control wiretap may be used on line or load
side of the Rockwell 194U disconnects from 30-600A.
An acceptable method for terminating one of the AVT
sensor leads. Note terminal adapters are sold in packages
of 2.