Cut Sheet

VeriSafe
Absence of Voltage Tester
3
Voltage indicators warn of hazardous voltage, but cannot be used to confirm if equipment is de-energized. Absence
of voltage testers are permanently-mounted test devices designed to verify that a circuit is de-energized prior to
opening an electrical enclosure containing electrical conductors and circuit parts.
More than a Voltage Indicator
Absence of Voltage Testers are Fail-Safe and Reliable
Test each phase conductor or circuit part phase-to-phase and phase-to-ground for absence of voltage
Built-in test circuit verifies operation on a known voltage source before and after absence of voltage test
Verifies installation of hardwired test leads before and after absence of voltage test
Functional safety principles ensure hardware and firmware are designed to prevent and control dangerous
failures of safety functions
Installed device ensures tester is rated for the application and is less susceptible to damage than
portable testers
Automated test sequence helps reduces operator errors
RED indicators illuminate
when hazardous AC voltage
is present.
Upstream Power: ON
When voltage is not detected,
indicators are not illuminated.
This does not guarantee the
absence of voltage.
Upstream Power: OFF
Pressing the "TEST" button initiates
the voltage test, indicated by the
flashing YELLOW caution indicator.
Upstream Power: OFF
GREEN indicator illuminates
only when the absence of
voltage has been verified.
Upstream Power: OFF