Cut Sheet
Table Of Contents
- General Product Information
- Installation/System Requirements
- Operation
- Standards & Ratings
- Functional Safety
- Indicator – Battery
- Indicator Module
- Isolation Module
- Sensor Leads
- AVT System Cables
- Access Control Kit
- Questions and Answers
- General Product Information
- GP01 Will voltage be present on the door when VeriSafe is installed?
- GP02 Does the VeriSafe AVT have internal short circuit protection?
- GP03 How should the VeriSafe AVT be disposed of at end of life?
- GP04 Does the VeriSafe AVT device have digital integrated circuitry?
- GP05 What is the absence of voltage threshold?
- GP06 Does the AVT detect ground faults?
- GP07 Does VeriSafe detect “stray” or inductive voltage in the 0-50V range?
- GP08 Is the device protected from static electricity?
- GP09 Is the VeriSafe Absence of Voltage Tester protected from power surges?
- GP10 What is the expected product life of the VeriSafe AVT?
- GP11 Can VeriSafe be used in an outdoor environment application?
- GP12 What is the voltage detection range of the VeriSafe AVT?
- GP13 Does the VeriSafe AVT have preventative maintenance (PM)?
- Installation/System Requirements
- IS01 Is overcurrent protection required for the VeriSafe Absence of Voltage Tester?
- IS02 Will installation of VeriSafe Absence of Voltage Tester affect the short circuit current rating (SCCR) of my equipment?
- IS03 Is the VeriSafe AVT a power circuit?
- IS04 Can the VeriSafe Absence of Voltage Tester be installed on a single-phase system?
- IS05 Can the VeriSafe Absence of Voltage Tester be installed on a DC system?
- IS06 Will the VeriSafe AVT detect improper installation?
- IS07 Can the AVT be installed to monitor the output of a Variable Frequency Drive (VFD)?
- IS08 Can VeriSafe be retrofit into existing equipment? Will this void the UL listing?
- IS09 Should the VeriSafe AVT device be installed on the Line side or Load side of the equipment disconnect?
- IS10 Is it acceptable to use a single VeriSafe AVT device on a main panel to provide absence of voltage protection for downstream panels?
- IS11 Does VeriSafe operate differently on solidly grounded and high resistance grounded systems?
- IS12 How does the VeriSafe AVT satisfy the NEC tap rule?
- IS13 What is the withstand and impedance rating of the AVT?
- IS14 Can the VeriSafe AVT be used on 4-pole systems?
- IS15 Can VeriSafe be installed in systems utilizing parallel runs?
- IS16 Can VeriSafe be installed in ungrounded systems?
- Operation
- OP01 Does the VeriSafe Absence of Voltage Tester verify it is operating satisfactorily before and after verifying the absence of voltage?
- OP02 Why does the yellow Caution Indicator flash at the end of a failed test procedure?
- OP03 Is PPE required to initiate an absence of voltage test with the VeriSafe Absence of Voltage Tester?
- OP04 Is PPE required to open an enclosure if the VeriSafe Absence of Voltage Tester confirms the absence of voltage (green light)?
- OP05 How does the VeriSafe Absence of Voltage Tester verify that sensor leads are in contact with phase conductors and ground?
- OP06 Will VeriSafe indicate the difference between residual voltage and nominal voltage?
- OP07 How would an operator know if nominal voltage is detected?
- OP08 Are users protected from hazardous voltage when using the AVT?
- OP09 Does the VeriSafe AVT device search for stored energy in VFDs, capacitors, or UPS devices?
- OP10 How do you know that the test circuit is working?
- OP11 Does VFD or MCC noise affect the device?
- OP12 Can VeriSafe be used to ensure that energy stored in the capacitors in a variable frequency drive (VFD) has dissipated?
- OP13 What is the “known voltage source” used to verify that the VeriSafe Absence of Voltage Tester is operating satisfactorily?
- OP14 What happens if VeriSafe is exposed to temperatures beyond its max rating of 60 C? Will VeriSafe stop working? How will it react?
- Standards & Ratings
- SR01 Does the VeriSafe AVT meet the requirements for permanently mounted absence of voltage testers described in NFPA 70E?
- SR02 What are the EMC ratings and test levels for VeriSafe?
- SR03 What is the operating temperature range of the VeriSafe AVT device?
- SR04 Do the door mounted Indicator module and DIN mounted Isolation module have different operating temperature ranges?
- SR05 What is the withstand rating of the AVT?
- SR06 What is the impedance rating of the AVT?
- SR07 Does VeriSafe meet the requirements for OSHA 1910.147 LOTO?
- SR08 What is the Performance Level (PL) rating of VeriSafe?
- SR09 Does VeriSafe have an officially published SCCR?
- SR10 Should the VeriSafe AVT be de-rated at higher altitudes?
- Functional Safety
- Indicator – Battery
- IB01 How long will the battery last?
- IB02 Where can a replacement battery for the indicator module be obtained?
- IB03 Do I have to de-energize my equipment to replace the battery?
- IB04 If the threshold is 3.0V, why do I have to verify that my de-energized line voltage is below 1.5V before installing?
- IB05 How many grams of Lithium does the VeriSafe AVT Indicator battery contain?
- Indicator Module
- Isolation Module
- IM01 What are the purpose of the output contacts on the Isolation Module?
- IM02 What is the rating of the Isolation Module output contacts?
- IM03 Is the Isolation Module serviceable?
- IM04 Is the Isolation Module conformal coated?
- IM05 At what voltage do the phase indicator lights turn off?
- IM06 What is the heat dissipation for the vertical and horizontal mounting of the isolation module?
- Sensor Leads
- SL01 Why are there two sensor leads per phase/ground?
- SL02 Why is it necessary to physically separate the two sensor leads during installation?
- SL03 Can the AVT Sensor Leads be extended?
- SL04 Can the AVT Sensor Leads be shortened?
- SL05 Is there a minimum or maximum distance required between installed sensor leads?
- SL06 Can one set of sensor leads be terminated on the line side of phase conductors and the other set of sensor leads be terminated on the load side?
- SL07 How should the VeriSafe Sensor leads be connected to a busbar?
- SL08 What methods can I use to terminate the sensor leads connected to power conductors in my equipment?
- SL09 Are ferrules required when installing sensor leads?
- AVT System Cable
- Access Control Kit
- AC01 What types of equipment can the VeriSafe™ Access Control Kit be installed in?
- AC02 How is the electronic latch powered?
- AC03 How much force can the electronic latch sustain?
- AC04 What is the lifespan of the VS-ACK-BATTERY?
- AC05 Is the VS-ACK-BATTERY replaceable?
- AC06 How do I access my panel if I lose power, or my electronic latch malfunctions?
- AC07 Can the wire harness included with the VeriSafe Access Control Kit be extended?
- AC08 Do I need a different mechanical override key for each VeriSafe™ access control kit?
- General Product Information
PANDUIT – FOR PUBLIC USE | January 15, 2020 | P: 800-777-3300 | www.panduit.com
article 240.21(B)(1)(b) Exception (NFPA 70:2017). This rule allows a tap of no more than 10 feet on a
feeder circuit without the need for overcurrent protection.
Other local wiring codes and regulations may require use of overcurrent protection. Always follow
applicable codes and standards when installing the device. The VeriSafe AVT can be installed safely with
overcurrent protection. When installing overcurrent protection with the VeriSafe AVT, it is important to
install one overcurrent protection device for each of the six sensor leads. Overcurrent protection should
not be installed with the two green ground leads. Do not install multiple lead wires on one overcurrent
protection device in a configuration that would leave lead wire pairs electrically connected in the event
that the overcurrent protection is in the open state. Top of the Document
IS02 Will installation of VeriSafe Absence of Voltage Tester affect the short circuit current rating
(SCCR) of my equipment?
The VeriSafe Absence of Voltage Tester is suitable for use on circuits capable of delivering up to 300,000
rms symmetrical amperes at 600V or less. AVTs listed to UL 1436 are required to operate as a
galvanically isolated secondary circuit that is isolated from the circuit conductors by use of a
transformer, optical isolator, or limiting impedance, or other similar means. This is intended to reduce
the risks of both electric shock and thermal hazard. These galvanic isolation circuits allow very limited
current flow, if any, through the AVT. Top of the Document
IS03 Is the VeriSafe AVT a power circuit?
The VeriSafe AVT is not part of the current carrying power circuit. It is a measuring device to determine
the absence of voltage in the power circuit. VeriSafe AVT detects the voltage of the three-phase power
circuit, but the current from the power circuit does not flow through VeriSafe. The VeriSafe AVT is
similar to a voltmeter, testing the circuit voltage without actually being in the power circuit current
path. In the event of a short circuit fault, the short circuit current does not flow through the VeriSafe
and no short circuit current rating (SCCR) is required.
IS04 Can the VeriSafe Absence of Voltage Tester be installed on a single-phase system?
The tester is designed primarily for three-phase systems, but can also be installed on single-phase
systems. Refer to schematics in the Instruction Manual. Top of the Document
IS05 Can the VeriSafe Absence of Voltage Tester be installed on a DC system?
The tester is primarily designed for three-phase AC systems, but it can be installed on a DC power
system. When installed in a DC system, the AVT is not polarity specific. If installed on a DC system, there
are no differences in the absence of voltage test function. However, the voltage presence indicators are
designed to illuminate when AC voltage is detected. The presence of DC voltage will not be indicated.
Refer to Installation Schematics in the Instruction Manual for further details. Top of the Document
IS06 Will the VeriSafe AVT detect improper installation?
The AVT will detect lack of continuity between the two leads for each phase, and between the two
grounding leads. Installation must be performed per the installation instructions by a qualified
electrician who must verify proper installation and operation of VeriSafe as described in the Instruction
Manual. Top of the Document










