IM02 What is the rating of the Isolation Module output contacts?
The output contacts have the following specifications:
Two channel, single-pole, normally open solid state relay
Relay closure upon absence of voltage verification
5000 V
rms
Input/output Isolation
Contacts rated for 30V AC/DC
Load Current 80 mA AC rms / mA DC
On-Resistance 30 Ω (max)
Compatible with up to 16 AWG (1 mm
2
)
SIL3 compliant
Duty Cycle: 10 seconds per test cycle
Load Current Peak: t=10ms, ±350mA
Off-State leakage current: 1 μA
Switching Speeds: @IF=5mA and VL=10V, Turn-On 2ms, Turn-off 1mS Top of the Document
IM03 Is the Isolation Module serviceable?
No. The Isolation module is a factory sealed unit and contain no serviceable parts. Top of the Document
IM04 Is the Isolation Module conformal coated?
Yes, the isolation module circuit boards are conformal coated. Top of the Document
IM05 At what voltage do the phase indicator lights turn off?
For voltages greater than 30VAC, the red indicator LEDs will be visible However, the red indicators may
be visible but dim between 18VAC and 30VAC. Top of the Document
IM06 What is the heat dissipation for the vertical and horizontal mounting of the isolation module?
2.14 Wats is the power (heat) dissipation at 600 Volt Y-installation, and 0.72 Wats in a 600V Volt Delta-
installation (typical US power distribution system). Top of the Document
Sensor Leads
SL01 Why are there two sensor leads per phase/ground?
VeriSafe is provided with a total of (8) 14 AWG sensor leads (two sensor leads for each phase conductor
and ground connection point). The second lead on each phase provides the ability for the AVT to verify
that it is in contact with the circuit conductors (each phase and ground) when the absence of voltage
test takes place. It is also part of the mechanism that is used to “test-the-tester” to validate that the AVT
is functioning. Top of the Document
SL02 Why is it necessary to physically separate the two sensor leads during installation?
Sensor leads for each phase and ground must not be in direct contact with each other in order for the
AVT to function properly. If the sensor leads are shorted, it is possible to defeat the installation test.