IB04 If the threshold is 3.0V, why do I have to verify that my de-energized line voltage is below 1.5V
before installing?
This is necessary because of the tolerance range for the threshold value. Accounting for that tolerance,
if voltage is greater than 1.3V when a circuit is de-energized, there is a possibility that the green Absence
of Voltage indicator will not illuminate. Top of the Document
IB05 How many grams of Lithium does the VeriSafe AVT Indicator battery contain?
Approximately 0.7 grams. Top of the Document
Indicator Module
NM01 What is the purpose of the Indicator Module?
The Indicator Module is designed to be mounted to an enclosure wall with part of it penetrating to the
outside for user interaction. Minimizing the electronics in this module helps keep the form factor
relatively small, which enables the user to install in a standard 30mm knockout and in relatively shallow
electrical enclosures. Top of the Document
NM02 Is the Indicator Module serviceable?
The battery is designed to be user replaceable. In addition, the o-rings can be replaced.
Top of the
Document
NM03 What will happen if an indicator fails?
The system has been designed to be fail-safe which is why the absence of voltage confirmation is
provided with an active indicator. Long-life LEDs were selected for the indicators. The green light only
remains on for a few seconds after the test, so it is unlikely that it would fail. The green indication
consists of multiple LEDs, if one would burn out the others would still operate. If for some reason all of
the green LEDs would burn out before the life of the product, the indicator module could be replaced, or
you would proceed to verify the absence of voltage with a handheld tester. Top of the Document
NM04 Why does the Yellow Indicator flash when I install a battery?
The battery tray includes a connector that is disconnected when the tray is withdrawn from the housing.
When the battery tray is pushed back into the housing, the re-connection initiates a self-test. Top of the
Document
NM05 What is the maximum panel thickness that the VeriSafe indicator module can be installed in?
The maximum panel thickness is 0.25” (6.3mm). there is no minimum panel thickness.
Isolation Module
IM01 What are the purpose of the output contacts on the Isolation Module?
The VeriSafe outputs are two channel, single-pole, normally open solid state relay contacts for optional
use. They are normally open and close only when the green light is illuminated. By wiring to these
contacts, you can use VeriSafe as an input to a control system as well as log when the absence of voltage
has been verified. Top of the Document