Cut Sheet
Pan-Way
®
T-70 Surface Raceway System
T-70
Internal Area = 5.15 Sq. In.
T70B T70C
T-70 Raceway
Wire Fill
Raceway
Type and
Configuration
Fill
Area
(in²)
Electrical Cables Data Grade Cables Coax Cables
Fiber Optic
Cable
14
AWG
12
AWG
10
AWG 24 AWG 24 AWG 24 AWG 24 AWG 24 AWG 24 AWG 24 AWG
RG6 RG59/u 2 StrandTHHN/THWN/T90
Cat. 5e -
Plenum
Cat. 5e -
Riser Cat. 6 Cat. 6A Cat. 6A Cat. 6A Cat. 6A (SD)
0.111 0.130 0.164 DIA = 0.193 DIA = 0.225 DIA = 0.240 DIA = 0.289 DIA = 0.300 DIA = 0.330 DIA = 0.240 DIA = 0.275 DIA = 0.242 DIA = 0.175
FILL FILL FILL FILL FILL FILL FILL FILL FILL FILL FILL
MAX MAX MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX
SPEC MAX SPEC MAX
SPEC MAX
(UL Temp Rise Test) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%)
T-70: No
devices
5.15 24 20 15 70 105 51 77 45 68 31 47 29 43 24 36 45 68 34 52 44 67 85 128
T-70: Power
and data
using the
three-sided
hanging box
and device
bracket
0.86 14 11 7 ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** **
1.72 ** ** ** 23 35 17 25 15 22 10 15 9 14 8 12 15 22 11 17 14 22 28 42
T-70: Data only
(Screw-On
Faceplates)
3.67 ** ** ** 50 75 36 55 32 48 22 33 20 31 17 25 32 48 24 37 31 47 61 91
T-70: Data
only (Snap-On
Faceplates)
4.71 ** ** ** 64 96 47 71 41 62 28 43 26 39 22 33 41 62 31 47 40 61 78 117
T-70: Power
and data
using the
Workstation
Outlet Center
™
Offset Box
0.91 14 11 7 ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** ** **
3.12 ** ** ** 42 63 31 47 27 41 19 28 17 26 14 21 27 41 21 31 27 40 51 77