Cut Sheet

Wire Fill
Pan-Way
®
Twin-70 Surface Raceway System
Twin-70 Lineart
TWIN-70
Left Internal Area = 4.59 Sq. In.
Right Inrenal Area = 4.59 Sq. In.
T702B T70C
T702B T70C
Raceway Type
and
Configuration
Fill
Area
(in²)
Electrical Cables Data Grade Cables Coax Cables
Fiber Optic
Cable
14
AWG
12
AWG
10
AWG
24 AWG 23 AWG 26 AWG 23 AWG
RG6 RG59/u 2 Strand
THHN/THWN/T90 Cat. 5e Cat. 6 Cat. 6A (SD) Cat. 6A
0.111 0.130 0.164 DIA = 0.193 DIA = 0.240 DIA = 0.240 DIA = 0.300 DIA = 0.275 DIA = 0.242 DIA = 0.175
FILL FILL FILL FILL FILL FILL FILL FILL
MAX MAX MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX SPEC MAX
(UL Temp Rise Test) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%) (40%) (60%)
Twin-70: Power
and data (no
terminations)
2.05 28 42 18 27 18 27 11 17 13 20 17 26 34 51
1.43 16 16 15
Twin-70: One
channel (no devices)
4.59 62 94 40 60 40 60 25 38 30 46 39 59 76 114
Twin-70: Data only
(Screw-On Faceplate)
3.11 42 63 27 41 27 41 17 26 20 31 27 40 51 77
Twin-70: Power only
(Screw-On Faceplate)
3.32 15 13 13
Twin-70: Data only
(Snap-On Faceplate)
4.14 56 84 36 54 36 54 23 35 27 41 36 54 68 103
Twin-70: TVSS Power
(Snap-On Faceplate)
2.33 16 16 14
Note: Cable diameters shown are industry averages and not necessarily Panduit specific, except for Cat. 6A (SD).
www.panduit.com