Specifications
Networked and Environmental Monitored POU
Version 1.0
5
Specifications
Overview
The PViQ Networked and Environmental POUs are rack level POUs with circuit monitoring via a built-in
web server in a self-contained unit. Web pages, including graphs, are generated by the unit to monitor
power and environmental conditions within the cabinet. No software other than a web browser is required
for operation and several data formats are available. In the PViQ Networked and Environmental POUs,
built-in sensors monitor Voltage, Current, instantaneous and cumulative Power, as well as calculated
Power Factor. Optional external sensors and network cameras are also available.
Environmental
Temperature
Operating: 10°C (50°F) min 45°C (113°F) max
Storage: -25°C (-13°F) min 65°C (149°F) max
Humidity
Operating: 5% min 95% max (non-condensing)
Storage: 5% min 95% max (non-condensing)
Elevation
Operating: 0 m (0 ft) min 2000 m (6561 ft) max
Storage: 0 m (0 ft) min 15240 m (50000 ft) max
Electrical
See nameplate for unit ratings.
Receptacle Ratings
NEMA 5-15R or L5-15R 125 Volts, 15 Amp
NEMA 5-20R or L5-20R 125 Volts, 20 Amp
NEMA 6-20R or L6-20R 250 Volts, 20 Amp
IEC-320 C13 125/250 Volt, 15 Amp (North America) or 10 Amp (Global)
1
IEC-320 C19 125/250 Volt, 20 Amp (North America) or 16 Amp (Global)
1
1
Given ratings are per receptacle bank