User manual

Network-Enabled M Series Rack PDU User Manual
- 16 -
accordance with the instruction manual, may cause harmful interference to radio com-
munications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own
expense.
Changes/modifications not approved by the responsible party could void the users
authority to operate the equipment.
Environmental Specifications
l Operating Temperature: 0C to 40C
l Transportation Temperature: -10C to 70C
l Operating Humidity: 15% to 85% non-condensing
l Transportation Humidity: 5% to 90% non-condensing
Bonding
This product contains an external earthing screw with a star washer, which should be
used for supplementary Earth bonding to the rack metalwork.
Bonding
Minimum Requirements for Bonding Conductors
Up to and including 32A 12 AWG
Up to and including 63A 8 AWG
Up to and including 80A 6 AWG
Screw Size
Over 16A, less than or equal to 40A 5mm
Over 40A, less than or equal to 63A 6mm
64A 7mm