Network-Enabled M Series Rack PDU User Manual
- 15 -
Warning: For permanently connected equipment, a readily accessible disconnect
device should be incorporated external to the equipment.
Power distribution products must be protected by a branch circuit protective device rated
at the maximum rating of the product specified on the product rating label.
To avoid risk of overload, do not plug additional multiple outlet power distribution
devices into the power distribution unit socket outlets.
This equipment is intended only for installation and use in a Service Access Location in
accordance with the following installation and use instructions.
This equipment is designed to be installed on a dedicated circuit.
l The dedicated circuit must have circuit-breaker or fuse protection.
l Rack PDUs have been designed without a master circuit breaker or fuse to avoid
becoming a single point of failure.It is the customer’s responsibility to provide
adequate protection for the dedicated power circuit.Protection of capacity equal to
the current rating of the Rack PDU must be provided and must meet all applicable
codes and regulations. In North America, protection must have a 10,000A interrupt
capacity.
Warning:Always disconnect the power supply cord before opening to avoid elec-
trical shock.
DANGER: High leakage current!Earth connection is essential before connecting
supply!
DANGER: Double Pole/Neutral Fusing: The plug on the power supply cord must
be installed near the equipment and must be easily accessible.
Rules
These limits are designed to provide reasonable protection against harmful interference
when the equipment is operated in a commercial environment. This equipment gen-
erates, uses, and can radiate radio frequency energy and, if not installed and used in