SmartZone™ Network-Enabled M Series Rack PDU User Manual Release 1.0 Issue 1.
Network-Enabled M Series Rack PDU User Manual Copyright © 2014 Panduit Corp. All rights reserved. No part of this book shall be reproduced, stored in a retrieval system, or transmitted by any means, electronic, mechanical, photocopying, recording or otherwise, without written permission from Panduit. No patent liability is assumed with respect to the use of the information contained herein.
Network-Enabled M Series Rack PDU User Manual Table of Contents SmartZone™ Network-Enabled M Series Rack PDU Contacting Panduit Symbols Used Equipment Overview Model Numbering Format Model Numbers Pre-Installation Product Inspection Installation Before You Begin Standard Accessories Mounting Hardware: Cables/Adapters: Hardwire PDU installation instructions Unterminated Cord PDU installation instructions Optional Accessories SmartZone Environmental Sensors: Additional Required Items Safety Precautions Serv
Network-Enabled M Series Rack PDU User Manual IPv4 Address Configuration The DHCP configuration (Dynamic Addressing provided by Infrastructure) Static Configuration (Manual Addressing) IPv6 Address Configuration AutoConfig only (link local addressing) Static configuration (manual addressing) DHCPv6 configuration (dynamic addressing provided by infrastructure) Accessing the appliance via a web browser using IPv6 HTTP SNMP NMS SNMP Receivers SNMP Trap Description Text Format Users Email Alerts Time Settings
Network-Enabled M Series Rack PDU User Manual SmartZone™ Network-Enabled M Series Rack PDU Network-Enabled M (Monitored) Series Rack PDUs integrate with the Panduit PIM Software Platform and other SmartZone applications to enable intelligent management of in-cabinet power usage.
Network-Enabled M Series Rack PDU User Manual -6- Symbol | Description ON O OFF
Network-Enabled M Series Rack PDU User Manual Equipment Overview The power inlet/cord(s) connects the PDU to the electrical power source. On metered PDUs, the LCD displays the current load for each input feed or electrical phase per input feed. l l One shielded RJ45 connector for Ethernet connection Two unshielded RJ45 connectors for SmartZone™ sensors (For a list of supported sensors, see "Optional Accessories".
Network-Enabled M Series Rack PDU User Manual Letter E What It Represents Any numeral, 1-7, indicating the number of output circuit breakers F Any letter, A-Z, indicating the type of overload protection provided for the outlets GH Any two numerals, 01-45, indicating the number of output receptacles provided JK The letter ‘A’ or ‘B’ followed by any letter, A-Z, indicating the type and quantity of output receptacles provided L Any numeral, 0-9, or any letter, A-Z, indicating the length of the power
Network-Enabled M Series Rack PDU User Manual Part Number Q1N1B3H0A30AHA0 Q1N1B3H0A30AXA0 Q1N2B1J0A30AHA0 Q1N2B1L2N30AHA0 Q1N2B1M2M24AKA0 Q1N2B1N3N30AHA0 Q1N2B1P3N30AHA0 Q1N2B2C3N30AHA0 Q1N2B2P6M30AHA0 Q1N2B2Q0A30AHA0 Q1N2B2T6N30AHA0 Q1N2B2W6N30AHA0 Q1N2B2W6N30APA0 Q1N2B3J2M30AHA0 Q1N2B4E3N30AEA0 -9-
Network-Enabled M Series Rack PDU User Manual Pre-Installation The Rack PDU products covered by this guide are designed to be installed within EIA racks and cabinets. Use of this product in other applications is acceptable, but other precautions may be required to allow for specific installations not covered by this guideline. Product Inspection Inspect the product prior to installation. If the product has any visible signs of damage, please contact the supplier.
Network-Enabled M Series Rack PDU User Manual Installation Before You Begin Before installing your PDU, refer to the following lists to ensure that you have all the items shipped with the unit as well as all other items required for proper installation.
Network-Enabled M Series Rack PDU User Manual 3. Ensure conductors are stripped adequately, exposing 15mm of copper. 4. Conductors shall be connected in-line with the terminal markings provided as shown below (Line 1 = X; Line 2 = Y; Line 3 – Z). Ensure screws are secure for each conductor by applying a torque of 2.3 N-m (20 in-lb.). 5. Ensure conductors have enough slack (none should be under tension). 6. Feed grommet cap down cord and secure to input gland.
Network-Enabled M Series Rack PDU User Manual Gland Size Grommet Cap Torque M16 1.5 N-m (13 in-lb.) M20 3.0 N-m (27 in-lb.) M25 M32 4.0 N-m (35 in-lb.) M40 15 N-m (132 in-lb.) M50 20 N-m (177 in-lb.) M63 30 N-m (266 in-lb.) 7. Re-install removable cover plate with the screws removed in step 1. 8. Connect the other end of the power cord to a suitably rated disconnect device. 9. Switch utility circuit breaker “On”.
Network-Enabled M Series Rack PDU User Manual Optional Accessories SmartZone Environmental Sensors: l l l l l l l l Smoke Sensor Humidity Sensor Water Rope Sensor Door Sensor Temperature Sensor Water Contact Sensor Air Flow Sensor Passive Infra-Red Motion Detector Additional Required Items l l l Flathead and Phillips screwdrivers Appropriate local AC power receptacle to power the PDU Local active Ethernet port to communicate with the PDU Safety Precautions This section contains important safety and reg
Network-Enabled M Series Rack PDU User Manual Warning: For permanently connected equipment, a readily accessible disconnect device should be incorporated external to the equipment. Power distribution products must be protected by a branch circuit protective device rated at the maximum rating of the product specified on the product rating label. To avoid risk of overload, do not plug additional multiple outlet power distribution devices into the power distribution unit socket outlets.
Network-Enabled M Series Rack PDU User Manual accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense. Changes/modifications not approved by the responsible party could void the user’s authority to operate the equipment.
Network-Enabled M Series Rack PDU User Manual Mounting There are two mounting options for Rack RDUs l l Vertical Mounting Horizontal Mounting Instructions for each mounting option are detailed below. Vertical Mounting The product is intended to be installed using the tool-less mounting buttons. These buttons locate in the fixing holes provided as shown in the following figure.
Network-Enabled M Series Rack PDU User Manual - 18 -
Network-Enabled M Series Rack PDU User Manual PDU Bracket for 4-Post Racks - 19 -
Network-Enabled M Series Rack PDU User Manual PDU Bracket for 2-Post Racks - 20 -
Network-Enabled M Series Rack PDU User Manual Horizontal Mounting This product is intended to be installed using the rack's RU mountings via the brackets found at either end of the PDU with the accessory screws provided listed below.
Network-Enabled M Series Rack PDU User Manual Hardware LCD Display The display shows the firmware version number, device model number, serial number, MAC Address, IP Address, and electrical readings. The display automatically scrolls through the readings.
Network-Enabled M Series Rack PDU User Manual Mode Button Operation Bootloader Startup When the user presses and holds the Mode button, the Display Backlight switches to one blink per second, indicating the bootloader is waiting for one of the following operations. l l l If the user releases the Mode button after two blinks, the backlight goes solid-on and stays in the bootloader, entering the “firmware recovery mode”. See the "Firmware Recovery Mode" section (below) for more details.
Network-Enabled M Series Rack PDU User Manual The application stays in this mode for at least 5 seconds. If no button operation is detected, the application continues to normal system operation. If the customer presses and holds the Mode button for 5 seconds, the following message displays on the LCD: Hold MODE button more than 5 seconds to reset to defaults If the customer continues to press and hold the Mode button, the following message displays on the LCD: Reset to defaults is detected.
Network-Enabled M Series Rack PDU User Manual Graphical User Interface The Panduit Network Enabled Rack PDU provides access to configuration, power, and sensor data through a Graphical User Interface (GUI), using a standard browser. There are several ways to connect to the device's GUI, depending on your network configuration and the firmware revision of the device. If the PDU has firmware revision 2.3.03 (or earlier), Static IP is the default. The configuration settings in this case are: IPv4 Address:192.
Network-Enabled M Series Rack PDU User Manual The default login and password are: Login:admin Password:admin After successful login, the GUI opens to the Overview page.
Network-Enabled M Series Rack PDU User Manual There are three modules within the GUI, each providing access to a different area within the PDU. The modules are: l l l Set Up Input Sensors Power To select a module, click the appropriate label along the top of the display. The menu items that appear on the left hand side of the screen will change depending on the module selected.
Network-Enabled M Series Rack PDU User Manual Setup When the setup module is selected, the following menu items appear along the left hand side of the display.
Network-Enabled M Series Rack PDU User Manual IP Configuration System Name System Location The name of the PDU The location of the PDU Contact Name A person to contact regarding the PDU Config Protocol Select the configuration protocol IP Address Subnet Mask Gateway The IP address of the PDU The Subnet Mask for the PDU IP Address The Gateway for the PDU IP Address IPv4 Address Configuration There are several kinds of IPv4 address configurations that you can choose from.
Network-Enabled M Series Rack PDU User Manual The DHCP configuration (Dynamic Addressing provided by Infrastructure) l The DHCPv4 client allows the user to obtain IPv4 configuration information from a DHCPv4 server. The functions that the DHCPv4 client performs include: l Basic server discovery and address assignment. l Address renewal and rebinding. l Address deprecation when the preferred lifetime expires. l Address removal when the valid lifetime expires.
Network-Enabled M Series Rack PDU User Manual DHCPv6 configuration (dynamic addressing provided by infrastructure) The DHCPv6 client allows the user to obtain IPv6 configuration information from a DHCPv6 server and works concurrently with stateless address autoconfiguration.
Network-Enabled M Series Rack PDU User Manual To choose the access method, click the corresponding radio button and enter the appropriate Port number. Typically the Port does not need to be changed from its default setting (80 for HTTP or 443 for HTTPS). HTTP or HTTPS access methods can be used. However, HTTPS is recommended for security. When you save any changes to this page, you will see the following message: After Saving, would you like to restart the unit? Click 'OK' to restart, otherwise 'Cancel'.
Network-Enabled M Series Rack PDU User Manual Both SNMPv2c and SNMPv3 protocols are supported simultaneously. You must enter the credential information for any device that needs to communicate with the unit via Simple Network Management Protocol (SNMP). Select the SNMP version settings you wish to edit from the drop-down menu.
Network-Enabled M Series Rack PDU User Manual Access Permission Settings Read Only Read / Write Permits the NMS to use only GET commands Permits the NMS to use both GET and SET commands SNMP Receivers The SNMP Receivers page displays information for all devices that receive SNMP traps sent from this unit. Enter the IP address and Community String for any device that will be required to receive SNMP traps. Usually any SNMP NMS entries should also be entered here.
Network-Enabled M Series Rack PDU User Manual Receive Traps Settings range of traps Receive traps – causes the unit to issue traps if there is Enabled (Incl. Auth Fails) an unauthorized attempt to access the unit’s SNMP functions. The version of trap/notification can be selected from the dropdown menu under Trap Version. SNMP Trap Description Text Format SNMP Traps are detected when certain events are detected. The format of the generated text messages is explained below.
Network-Enabled M Series Rack PDU User Manual SNMP Trap Text Format On, Information Off, Cleared, Unknown. ::= ::= "(" ")" Data source. Example: “Input 01”. When available, the number of the sensor Port the alert came from. ::= Event description of the reason for the trap. See the “User Text” strings on the Trap Configuration pages or the per-sensor configuration pages.
Network-Enabled M Series Rack PDU User Manual The PDU GUI comes with the Administrator login predefined as: l l Login:admin Password:admin To add new users, enter a unique Username and Password for each, then select the desired level of permission. You may configure up to 20 users. Level of permission for each user can be selected from the drop-down menu on the right.
Network-Enabled M Series Rack PDU User Manual Email Alerts On this page, you can edit email alert settings for traps. You may set up to 10 email receivers. Email Alerts SMTP Relay Server The IP Address of the SMTP Server From Address Reply-To Address Address from which the alert emails are sent Address to which the email receivers can reply Destination Address Address that will receive the email alerts Enabled Toggle the check box to enable or disable alerts to each address.
Network-Enabled M Series Rack PDU User Manual Time Settings The Time Settings page allows you to view or edit the current date and time. Select the correct day, month, and year from the dropdown menus, and verify the local time. If you want to change the time, you must check the Update time checkbox. Time Adjustments Select the correct time zone from the drop-down menu. l l Daylight Saving can be enabled or disabled by clicking the check box.
Network-Enabled M Series Rack PDU User Manual SNTP Servers - Simple Network Time Protocol synchronizes the clocks of computer systems over a network. Enter the IP address of an SNTP server, and specify (in hours) how often the time should be updated. l Syslog Servers This page allows you to view or edit information about the Syslog Servers currently being used. From the Enabled drop-down menu, you can choose which syslog servers are enabled. Fill in the following fields for each Syslog server.
Network-Enabled M Series Rack PDU User Manual Events The View Events page shows a history of events that have occurred, along with specific details about each event. To specify a range of events to view, select the desired year and month from the dropdown menus, then click Show. Date/Time, Type, User, and Event Data for each event are displayed. Events can be ordered Latest First or Earliest First by clicking the corresponding radio button.
Network-Enabled M Series Rack PDU User Manual Default Page Preferences From the dropdown menu, select the first page you want to open when a user logs in. The preset default page is the Overview page. Choose from the dropdown menu where the timestamp will be found on traps.
Network-Enabled M Series Rack PDU User Manual Restart Clicking the Restart option brings up the following screen: To restart the unit or restore to factory defaults, click the corresponding button. Note: Resetting to factory defaults will restart the device.
Network-Enabled M Series Rack PDU User Manual Input Sensors When the Input Sensors module is selected, the following items appear along the lefthand side of the display. Input Sensors Menu Options Status Defaults Configure Sensor Trap Text View information from connected input sensors View or edit default settings for input sensors Configure sensor inputs View or edit trap text Detailed information on each of these menu options can be found in the corresponding sections below.
Network-Enabled M Series Rack PDU User Manual Status Indicators All thresholds within limits Upper Control Limit reached/exceeded Upper Warning Limit reached/exceeded Lower Warning Limit reached/exceeded Lower Control Limit reached/exceeded This page may also display the strings "O/R" and "U/R" in place of the input sensor measurement. This indicates an over-range or under-range condition.
Network-Enabled M Series Rack PDU User Manual The Humidity Sensors screen displays default information as shown below. The Analog Voltage screen displays default information as shown below.
Network-Enabled M Series Rack PDU User Manual Explanations of the editable fields in the drop-down menus for Temperature, Humidity and Analog Voltage can be found in the table below. Defaults- Temperature, Humidity, and Analog Voltage The scaling factor is a value multiplied against the measured Analog Voltage to produce the Input Sensor measurement.
Network-Enabled M Series Rack PDU User Manual Defaults- Temperature, Humidity, and Analog Voltage and alarm purposes would be 42. This works in an identical way for both temperature and humidity sensors. The hysteresis default value to be applied to sensors is. The value specified is an offset from a sensor’s threshold values.
Network-Enabled M Series Rack PDU User Manual Normal State Defaults- Open/Close Contacts Normal state specifies the condition in which a contact is considered to be ‘Normal’, ‘Non-alarmed’ state. Devices such as smoke alarms and air conditioning units often have normally open contacts. In order to receive alarm indications from these types of units, setting normally open would cause alarms to be issued when the monitored contact closes.
Network-Enabled M Series Rack PDU User Manual Defaults- Open/Close Contacts an alarm is required to persist after an input changes from the Normal state to the Non-Normal state. Non-Normal to Normal (Negative Edge) This type of triggering may be used in situations where a momentary type input (e.g. shock sensor, PIR etc.), is used. Since these types of inputs are momentary any alarm condition which occurs, no matter how short, will persist until manually cleared.
Network-Enabled M Series Rack PDU User Manual Individual settings can be entered for each input channel. The drop-down menu options are identical to the Defaults page. Note: The important difference between the menus presented here and the menus presented on the Defaults page is that these settings are applied to individual channels. The drop-down menus can be opened and closed by clicking the corresponding arrows.
Network-Enabled M Series Rack PDU User Manual Enter text to be displayed for each type of trap.
Network-Enabled M Series Rack PDU User Manual Power When the Power module is selected, the following menu items appear along the lefthand side of the display. l l l l l Status Branch Monitoring (if the unit has breakers) Status 3-Phase (if the unit is 3-Phase) Thresholds Configure Status Single-Phase The Status screen displays information from a connected Single-Phase Power Device. Branch Monitoring If the power device has breakers, you will see the Branch Monitoring button as shown below.
Network-Enabled M Series Rack PDU User Manual Status 3-Phase If the device is 3-Phase, you will see the 3-Phase Status button as shown below. The 3Phase Status screen displays information from a connected 3-Phase Power Device. Many of the following pages use abbreviations for various units. A reference table is provided below for convenience.
Network-Enabled M Series Rack PDU User Manual Configure The Configure page allows you to view and configure Power Circuits. Depending on the type of unit, not all menu items shown below may be available. Clicking the configuration button – Cfg – for a circuit brings up a screen similar to the following.
Network-Enabled M Series Rack PDU User Manual Clicking on the arrows next to each option opens a drop-down similar to the following: Explanations of the editable fields within the drop-down menus can be found in the table below.
Network-Enabled M Series Rack PDU User Manual Configure Power Circuits Circuit Name The name of the chosen circuit. Upper Control Limit The value at which an Upper Control alarm will be issued. Upper Warning Limit The value at which an Upper Warning alarm will be issued. Lower Warning Limit The value at which a Lower Warning alarm will be issued. Lower Control Limit The value at which a Lower Control alarm will be issued.
Network-Enabled M Series Rack PDU User Manual Enter the desired text in the text box provided, and click the Save button to implement your customization.