Cut Sheet

www.panduit.com
Electrical performance: Certified channel performance in a 4-connector configuration up to
100 meters and exceeds ISO 11801 Class D and ANSI/TIA-568-C.2
Category 5e standards at swept frequencies up to 100 MHz
Certified component performance up to 100 meters and exceeds
the component requirement of IEC 61156-5 and ANSI/TIA-568-C.2
Category 5e component standards at swept frequencies up to
100 MHz
Conductors/insulators: Riser – 24 AWG solid copper insulated with HDPE
Plenum – 24 AWG solid copper insulated with FEP
Flame rating: Riser – UL 1666
Plenum – NFPA 262
PoE compliance: Meets IEEE 802.3af and IEEE 802.3at for PoE applications
Installation tension: 25 lbf. (110 N) maximum
Temperature rating: 32°F to 122°F (0°C to 50°C) during installation
-4°F to 167°F (-20°C to 75°C) during operation
Cable jacket: Flame-retardant PVC (CMR) or low smoke, flame-retardant,
fluoropolymer (CMP)
Cable diameter: Riser – 0.500 in. (12.7mm) nominal
Plenum – 0.455 in. (11.6mm) nominal
Cable weight: Riser – 132 lbs./1000 ft. (60 kg/395m)
Plenum – 142 lbs./1000 ft. (65 kg/305m)
Packaging: 1000 ft. (305m) on a wooden reel
Package tested to ISTA procedure 1B
technical information
specifications
Category 5e cable shall exceed ANSI/TIA-568-C.2
and IEC 66156-5 Category 5e component standards.
The construction shall be 24 AWG with HDPE (CMR)
or FEP (CMP) insulation. The copper conductors
shall be twisted in pairs with all 25-pairs covered
by a flame-retardant PVC (CMR) or low smoke,
flame-retardant, fluoropolymer (CMP) jacket.
applications
TX5500
UTP Copper Cable is a component
of the Panduit
®
TX5500
Copper Cabling
System. Interoperable and backward
compatible, this end-to-end system provides
design flexibility to protect network investments
well into the future. With certified performance
to ANSI/TIA-568-C.2 Category 5e and
ISO 11801 Class D standards, this system
is ideal for today's high performance
workstation applications.
Usage of the TX5500
Copper Cabling
System includes:
Ethernet 10BASE-T, 100BASE-T (Fast
Ethernet), 1000BASE-T (Gigabit Ethernet)
155 Mb/s ATM
Token Ring 4/16
Voice and multimedia systems
High-density voice and data applications for
backbone and cross connect installations
key features and benefits
Descending length Easy identification of remaining cable reduces installation
cable markings time and cable scrap
Third party tested Cable has been tested as part of the TX5500
Copper Cabling
System by an independent laboratory and complies with the
electrical channel requirements of the following standards:
ISO 11801 and ANSI/TIA-568-C.2
Tested beyond Cable has been characterized to 250 MHz, 150 MHz
the standards above the standard
TX5500
25-Pair Category 5e UTP
Copper Cable
TX5500
Copper Cabling System
TX5500
Copper Cable
Plenum: PUP5525*-UY
Riser: PUR5525*-UY
Mini-Com
®
TX5e
UTP
Jack Module
Jack Module: CJ5E88TG**
TX5e
UTP Patch Cords
Feet: UTPCH^Y
Meters: UTPCH^^MY
DP5e
Angled Patch Panels
24-port, 1 RU: DPA245E88TGY
48-port, 2 RU: DPA485E88TGY
DP5e
Flat Patch Panels
12-port: DP125E88TGY
24-port, 1 RU: DP245E88TGY
48-port, 2 RU: DP485E88TGY
Pan-Punch
110 Category 5e
Punchdown System
See website (www.panduit.com) or catalog for
complete system information.
Cable Prep Tools
Wire
snipping tool: CWST
Wire
stripping tool: CJAST
*Please contact customer service for
color availability.
**To designate color, add suffix IW (Off White),
EI (Electric Ivory), IG (International Gray),
WH (White), BL (Black), OR (Orange),
RD (Red), BU (Blue), GR (Green), YL (Yellow)
or VL (Violet).
^For lengths 1 to 20 feet (increments of one
foot) and 25, 30, 35, 40 feet, change the length
designation in the part number to desired
length. For standard cable colors other than Off
White, add suffix BL (Black), BU (Blue), GR
(Green), RD (Red), YL (Yellow), OR (Orange)
or VL (Violet) before the Y at the end of the
part number. For example, the part number for
a blue, 15-foot patch cord is UTPCH15BUY.
^^For lengths 1 to 10 meters (increments of
one meter) and 0.5, 1.5, 2.5, 15, 20 meters,
change the length designation in the part
number to the desired length. For standard
cable colors other than Off White, add suffix
BL (Black), BU (Blue), RD (Red), GR (Green),
YL (Yellow), OR (Orange) or VL (Violet) after
the M in the part number. For example, the part
number for a 15-meter patch cord with blue
boots is UTPCH15MBUY.
SPECIFICATION SHEET