J.3
Cable/Conduit Beam/Purlin Hangers/Hanging
Systems
Stud Wall Communication/
Low Voltage
Dry Wall Acoustical Miscellaneous Index
Sizing Information
Reference
Codes & Standards
Reference
Electrical Non-Metallic Tubing (ENT)
Trade
Nominal
Size
(In.)
Nominal
Inside
Dia.*
(In.)
Nominal
Outside
Dia.
(In.)
Min. Weight
of Conduit
Per 100 Ft.
(Lbs.)
Weight of
Conduit and
Conductors
Per 100 Ft.
(Lbs.)
0.50 0.56 0.84 11.00 33.10
0.75 0.76 1.05 14.00 54.80
1.00 1.00 1.32 20.00 86.30
1.25 1.40 1.66 19.00 136.30
1.50 1.55 1.99 27.00 186.80
2.00 2.03 2.38 32.00 261.80
*Per UL table NAE.3.
Schedule 40 PVC Plastic Pipe
Nominal
Pipe
Size
(In.)
Outside
Dia.
(In.)
Wall
Thickness
(In.)
Weight
of Pipe
Per Ft.
(Lbs.)
Weight
of Water
Per Ft.
(Lbs.)
0.13 0.41 0.07 0.04 0.02
0.25 0.54 0.09 0.07 0.04
0.38 0.68 0.09 0.10 0.08
0.50 0.84 0.11 0.15 0.1
0.75 1.05 0.11 0.20 0.20
1.00 1.32 0.13 0.30 0.40
1.25 1.66 0.14 0.40 0.60
1.50 1.90 0.15 0.50 0.90
2.00 2.38 0.15 0.60 1.40
2.50 2.88 0.20 1.00 2.10
3.00 3.50 0.22 1.30 3.20
3.50 4.00 0.23 1.60 4.30
4.00 4.50 0.24 1.90 5.50
All Threaded Rod (ATR)
Nominal
Size
and
Thread
Root Area
Design Load
SF = 5
In.
2
cm
2
Lbs. kN
1/4-20 0.03 0.17 240.00 1.07
5/16-18 0.05 0.29 400.00 1.78
3/8-16 0.07 0.44 610.00 2.71