Submittal

4
SmartZone
G5
Product Features
Monitored
Input
(MI)
Monitored
Switched
(MS)
Monitored
per
Outlet
(MPO)
Monitored
& Switched
per Outlet
(MSPO)
Design Features
• Low prole, space saving design
• Ultra low prole circuit breakers on most models
Adjustable tool-less mounting system
• Color-coded receptacles
• Locking IEC receptacles and locking power cord compatible
• Field rewireable input cord for front or top mounting
PDU Energy Metering and Monitoring
• PDU level watt-hour energy metering (kWh)
• PDU level power measurements (W)
• Input Phase level power measurements (V, A, VA, kWh, pf)
• Circuit breaker level current measurements
• High-accuracy, billing-grade metering capabilities
• Embedded memory log to record/view/report historical data
• User customizable alarm thresholds & notications
Outlet Level Switching
• Remote On/Off power control by individual outlet
• User-dened power-on time delay to sequence IT equipment
Automatic sequencing to avoid inrush current overload
• Outlet level user security with assignable roles and user access
Outlet Level Energy Metering
• Outlet level watt-hour energy metering (kWh)
• Outlet level power measurements (V,A,VA, W, pf)
• Outlet level information for Green Grid Level 3 PUE Calculations
Environmental & Security Management
• Optional Plug & Play environmental sensors including temperature,
humidity, dry contact and water leak
• User customizable alarm thresholds and notications
Physical Security Management
• Rack access monitoring with door contact switch
• User customizable alarm thresholds and notications
• Dry Contact accessory to activate strobe, beacon, or fan
Network Management and Local Display Interface
• Largest-in-class, high-visibility, OLED display
• Full featured network management and alerting capabilities
supporting HTTP, HTTPS, SSH, Telnet, SNMP, FTP and email
• Strong encryption, passwords, and advanced authorization options
including local permissions, LDAP/S, and Active Directory
• Daisy Chain up to 4 Rack PDUs and 32 environmental sensors
through a single IP address
Circuit Breaker Status Monitoring
Active monitoring and alarming of circuit breaker on/off status