Mid-Span Support for Wall Beams
Panduit recommends a mid-span support every 3,600mm (11.8’). The maximum distance without a mid-span
support is 4,800mm (16’).
Wall beams can be supported using any of the following:
--Mid-span cabinet support
--Threaded rod suspended from the ceiling
--Mid-span support post
Supporting Wall Beams using Mid-Span Cabinet Support
Thread the mid-span cabinet support rod through a M12 hex nut, a 1/2" washer, the wall beam, then through
another 1/2" washer, M12 hex nut and finally into the swiveling level mount.
View From Top
View From Side
Rod
(2) M12 Hex
Nuts
(2) 1/2"
Washers
Swiveling
Level Mount
Supporting Wall Beams using Threaded Rod
Wall beams can be supported using threaded rod suspended from the ceiling. Threaded rod can be attached
using the same holes as the Mid-Span cabinet support shown above.