Technical Bulletin
StructuredGround
™
Mechanical Connectors
5
Bronze Split Bolt Quad Clamp
Copper and Aluminum One-Hole Grounding Lay-in Lug
• Split bolt design allows easy insertion of perpendicular
conductors to speed installation
• UL 467 Listed and CSA Certied for direct burial in
earth or concrete
• UL Listed and CSA Certied for use up to 600 V and
temperature rated 90°C
• Each clamp accepts up to two conductors for a high
performance bond with faster installation
• Wire range-taking capability minimizes inventory
requirements, saves cost
• Made from high strength, electrolytic bronze to provide
reliable grounding connections
• Used for quick installation of a continuous
grounding conductor
• UL 467 Listed for grounding and bonding; copper body
lugs are UL Listed for direct burial in earth or concrete
(aluminum body lugs are not direct burial rated)
• cULus Listed for use up to 600 V and temperature
rated 90°C
• Wire range-taking capability minimizes inventory
requirements, saves cost
E
L
W
B
RATED
D
B
RATED
D
Part Number
Set Screw
Material
Conductor Size
Range (AWG)
Stud Hole Size
(In.)
Hex Key Size
(In.)
Figure Dimensions
(In.)
Std.
Pkg.
Qty.L W H
Copper Body
LICC4-22-C Stainless Steel #14 SOL – #4 STR 0.22 ** 1.16 0.39 0.87 100
Tin-Plated Copper body
LICC4-22TP-C Stainless Steel #14 SOL – #4 STR 0.22 ** 1.16 0.39 0.87 100
Tin-Plated Aluminum Body*
LIAC4-22-C* Stainless Steel #14 SOL – #4 STR 0.22 ** 1.06 0.39 0.78 100
LIAS1/0-14-L* Zinc Plated Steel #14 SOL – 1/0 STR 0.27 ** 1.50 0.61 1.10 50
LIAS250-56-Q* Zinc Plated Steel #6 SOL – 250 STR 0.33 1/4 2.20 0.80 1.70 25
AluminumCopper Tin-Plated Copper
*Not DB Rated
**Uses slotted head set screw.
The use of Panduit oxide inhibiting joint compound (CMP) is recommended for pad and conductor connections.
Part Number Conductor Size Range (AWG)
Figure Dimensions
(In.)
Tightening Torque
(In. – Lbs.)
Std.
Pkg.
Qty.E W L
SBQC1/0-X #6 SOL – 1/0 STR 0.75 1.50 2.00 #6 – #4 AWG – 165
#3 – #1 AWG – 275
1/0 AWG – 385
10
H
W
L
H
W
L