Cut Sheet
Trunk Type and Terminations
Both ends of a QuickNet
™
Fiber cable assembly include one of a range of factory
termination options – each end can be different and are selected based upon the
desired application of the trunk or harness within the data center.
Termination choices are:
• Duplex LC to Duplex LC
• PanMPO to PanMPO
• PanMPO to LC
• MPO to MPO
• MPO to LC
• Cassette to Cassette
• Cassette to MPO/Duplex LC
Insertion Loss is the amount of power lost at each mated pair of connectors. Standard
maximum insertion loss per connector pair:
• Multimode PanMPO to PanMPO: 0.50dB
• Multimode MPO to MPO: 0.50dB
• Multimode LC to LC: 0.25dB
• Singlemode MPO to MPO: 0.75dB
• Singlemode LC to LC: 0.35dB
Optimized insertion loss per connector pair:
• Multimode PanMPO to PanMPO: 0.35dB
• Multimode MPO to MPO: 0.35dB
• Multimode LC to LC: 0.15dB
Assembly Options
Options include:
• No Pulling Eye
• Pulling eye on one end (as shown in Figure 8)
• Pulling eye on both ends
A pulling eye is a loop of braided sleeve material that is applied to one or both ends of
the QuickNet
™
Trunk Assembly, and is used to pull the cable in the pathways
at deployment.
Figure 8 –
Pulling Eye Option
Connectors
Braided
Sleeving
Loop for
Pulling
Quicknet
™
Fiber
Trunk Assembly
www.panduit.com
10