Submittal
Panduit Corp. 2017  Testing Procedures PN614  version 1.0 (revised 6/2017)
For Technical Support: www.panduit.com/resources/install_maintain.asp 
Page 4 of 5 
5)  Select from the following Fluke Test Limits, for which warranty is desired: 
•  TIA Cat 6A Permanent Link  
•  ISO Class E
A
 Permanent Link  
6)  Begin testing your installed permanent link with the Fluke DSX-5000 Series Digital Cable 
Analyzer and save all test results.  
7)  Troubleshoot and repair any failing permanent links. Permanent links resulting in a PASS* 
are considered a PASS and will be acceptable for warranty. 
Note: The Fluke HDTDX analyzer and HDTDR test are very helpful when troubleshooting 
failing channels. Both can be found on the SINGLE TEST menu and will also run 
automatically when a failure occurs. Also make sure that Store Plot Data is set to Extended 
under Setup/Instrument settings. 
8)  Submit electronic permanent link test reports to the PANDUIT Warranty Department with all 
required warranty paperwork. A warranty will then be given based on passing test results. 
Note: PANDUIT recommends that installers install and test multiple permanent links before 
completing the entire system. 
Permanent Link Testing (Alternate Method) 
1)  Verify that your DSX-5000 Series tester has the most up-to-date software. The latest 
software updates can be found on the Fluke website at: 
http://www.flukenetworks.com/support/downloads/58119/DSX%2BCableAnalyzer%25E2%25
84%25A2%2BSeries 
2)  Perform a Set Reference procedure in the special functions prior to testing. Fluke Networks 
recommends that a Set Reference procedure be performed every 30 days to ensure the 
maximum accuracy of the test results. DSX Reference Module part# DSX-REFMOD, is 
recommended for Category 6A testing. 
For detailed instructions on Set Reference procedure, refer to Fluke Network’s DSX-5000 
Series Users Manual page 36, on “Set the Reference”. The link for the User’s Manual is: 
http://www.flukenetworks.com/support/manuals/58119/DSX%2BCableAnalyzer%25E2%2584
%25A2%2BSeries 
Note: Fluke Networks also recommends factory calibration once a year to ensure that the 
test tool meets or exceeds the published accuracy specifications. 
3)  Select the Fluke Permanent Link Adapter (DSX-PLA001) and attach it to the DSX-5000 
Series Main unit. 
4)  Select the Fluke Channel Adapter (# DSX-CHA004S) and attach it to the DSX-5000 Series 
Remote unit.  
5)  Select from the following Fluke Test Limits, for which warranty is desired: 
•  TIA Cat 6A Permanent Link  
•  ISO ClassE
A
 Permanent Link  
6)  Begin testing your installed permanent link with the Fluke DSX-5000 Series Digital Cable 
Analyzer. You will receive a warning for an adapter/test limit compatibility. Press YES to 
continue. Save all test results.  
7)  Troubleshoot and repair any failing permanent links. Permanent links resulting in a PASS* 
are considered a PASS and will be acceptable for warranty. 
Note: The Fluke HDTDX analyzer and HDTDR test are very helpful when troubleshooting 
failing channels. Both can be found on the SINGLE TEST menu and will also run 
automatically when a failure occurs. Also make sure that Store Plot Data is set to Extended 
under Setup/Instrument settings. 
8)  Submit electronic permanent link test reports to the PANDUIT Warranty Department with all 
required warranty paperwork. A warranty will then be given based on passing test results. 
Note: PANDUIT recommends that installers install and test multiple permanent links before 
completing the entire system. 