Installation Manual
For Technical Support: www.panduit.com/resources/install_maintain.asp
INSTALLATION INSTRUCTIONS
© Panduit Corp. 2018
FS128B
Page 3 of 16
Figure 4
Polarity label
(optional slack plate removed for clarity)
First, attach trunk cabling to the rear port of the
cassette or FAP to be installed. Note the polarity label
on the cassette and orient properly as needed.
Cassettes should be installed one at a time starting
with the bottom most slot on the right, as shown. To
install cassettes, insert into slot and push forward until
it snaps into place.
Populate the entire row across from right to left before
moving to the next row above. Repeat process until all
desired slots are filled.
MAXIMUM MODULE POPULATION
4-Port 6-Port 12-Port
Modules Modules Modules
FLEX1UPN04 18 -- --
FLEX1UPN06 -- 12 --
FLEX1UPN12 -- -- 6
FLEX2UPN04 36 -- --
FLEX2UPN06 -- 24 --
FLEX2UPN12 -- -- 12
FLEX4UPN04 72 -- --
FLEX4UPN06 -- 48 --
FLEX4UPN12 -- -- 24
Cassette Assembly (sold separately)
Figure 5
(optional slack plate removed for clarity)
Cassettes can be removed from the front of the patch
panel as needed for replacement or migration.
Disconnect patch cords from the front of the cassette.
Press latch away from the module and pull the module
forward. Once the module is pulled past the latch the
module can be completely removed.
Figure 6
Disconnect trunk cable from the rear of the cassette
and connect it to the rear of the replacement cassette.
Re-install cassette or MPO FAP opposite the way it
was removed. Align the rear of the cassette or MPO
FAP in the opening and push inward until the cassette
snaps into place. Re-attach patch cords (for cassette
changes).
Figure 7
MPO FAP
Port 1
1 6
If migrating to an MPO FAP, connect the MPO trunk
cable to the left most position, port 1.