OPERATION (WHEN CONTACTS ARE WELDED)
The table below shows the state of the other contacts when the current through the welded N.O. contact is 0 V and the Max.
applied voltage ( 120% V of rated coil voltage ) is applied to the coil through the welded N.C. contact.
■ 4poles
● 2FormA2FormB
State of other contacts
34 ( N.C. ) 56 ( N.C. ) 78 ( N.O. ) 910 ( N.O. )
Welded terminal No.
34 ( N.C. ) − > 0.5 > 0.5
56 ( N.C. ) − > 0.5 > 0.5
78 ( N.O. ) > 0.5 > 0.5 −
910 ( N.O. ) > 0.5 > 0.5 −
■ 6poles
● 4FormA2FormB
State of other contacts
34 ( N.C. ) 56 ( N.C. ) 78 ( N.O. ) 910 ( N.O. ) 1112 ( N.O. ) 1314 ( N.O. )
Welded terminal No.
34 ( N.C. ) − > 0.5 > 0.5 > 0.5 > 0.5
56 ( N.C. ) − > 0.5 > 0.5 > 0.5 > 0.5
78 ( N.O. ) > 0.5 > 0.5 −
910 ( N.O. ) > 0.5 > 0.5 −
1112 ( N.O. ) > 0.5 > 0.5 −
1314 ( N.O. ) > 0.5 > 0.5 −
● 3FormA1FormB
State of other contacts
34 ( N.C. ) 56 ( N.C. ) 78 ( N.O. ) 910 ( N.O. )
Welded terminal No.
34 ( N.C. ) − > 0.5 > 0.5 > 0.5
56 ( N.C. ) > 0.5 −
78 ( N.O. ) > 0.5 −
910 ( N.O. ) > 0.5 −
● 5FormA1FormB
State of other contacts
34 ( N.O. ) 56 ( N.C. ) 78 ( N.O. ) 910 ( N.O. ) 1112 ( N.O. ) 1314 ( N.O. )
Welded terminal No.
34 ( N.O. ) − > 0.5 > 0.5 > 0.5 > 0.5 > 0.5
56 ( N.C. ) > 0.5 −
78 ( N.O. ) > 0.5 −
910 ( N.O. ) > 0.5 −
1112 ( N.O. ) > 0.5 −
1314 ( N.O. ) > 0.5 −
> 0.5: Contact gap Min. 0.5 mm
Empty cells: Contact is ON or OFF state.
Note) Contact gaps are shown at the initial state. If the contacts change state owing to switching it is necessary to check the actual loading.
ASCTB317E 202204
Panasonic Industry Co., Ltd. Electromechanical Control Business Division
industrial.panasonic.com/ac/e/
Panasonic Industry Co., Ltd. 2022
ー 5 ー